background image

614-40096-00

10

Package content

Verify that the following additional items are included 
with the UPS:

 UPS

 Connection cable to AC power source (2200VA & 

3000VA models only)

 Connection cables for the protected equipment

 RS232 communication cable

 USB communication cable

 Safety instructions

 Quick start

 Cable locking systems

 Rack kit for 19-inch 4-post enclosures

 Two supports for tower position (tower feet)

 Communication card (optional)

 FlexPDU module 

(optional)

 Connection cables between FlexPDU module and UPS 

(

optional)

 HotSwap MBP module (optional)

 Connection cables between HotSwap MBP module 

and UPS (optional)

Summary of Contents for Eaton 5PX

Page 1: ...Eaton 5PX Advanced User Guide Copyright 2021 EATON All rights reserved 614 40096 00 5PX1500HRTG2 5PX2200HRTG2 5PX3000HRTG2 5PX3000HRTNG2 5PXEBM48RTG2 5PXEBM72RTG2...

Page 2: ...nt a risk of energy or electrical shock or burn from high short circuit current Observe proper precaution Batteries may contain HIGH VOLTAGE and CORROSIVE TOXIC and EXPLOSIVE substances Information ad...

Page 3: ...exPDU Power Distribution Unit optional module 15 3 7 Connection with a HotSwap MBP Maintenance ByPass optional module 15 4 Interfaces and communication 17 4 1 Control panel 17 4 2 LCD description 18 4...

Page 4: ...Recycling the used equipment 34 7 Troubleshooting 34 7 1 Typical alarms and faults 35 7 2 Silencing the alarm 37 7 3 Service and support 37 8 Specification and technical characteristics 37 8 1 UPS mo...

Page 5: ...utlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help UPS employing batteries with min V 2 case are intended for u...

Page 6: ...1 2 Benefits The Eaton 5PX uninterruptible power system UPS protects your sensitive electronic equipment from the most common power problems including power outages voltage sags impulsive transients...

Page 7: ...22 4 17 6x17 2x3 4 448x438x85 5 5PX2200HRTG2 62 2 28 2 23 7x17 2x3 4 603x438x85 5 5PX3000HRTG2 69 9 31 7 23 7x17 2x3 4 603x438x85 5 5PX3000HRTNG2 69 9 31 7 23 7x17 2x3 4 603x438x85 5 Description EBM...

Page 8: ...group critical equipment Outlet group programmable outlets USB communication port RS232 communication port Relay output contact Connector for ROO Remote On Off control and RPO Remote Power Off Slot f...

Page 9: ...ernal maintenance bypass 6 5 20R HotSwap external maintenance bypass 5 5 20R EFLXL1500R PDU1U EFLXL2000R PDU1U EFLXL2000R PDU1UL EFLXI3000R PDU1UIEC FlexPDU 12 5 15R FlexPDU 12 5 20R FlexPDU 5 L5 20R...

Page 10: ...ted equipment RS232 communication cable USB communication cable Safety instructions Quick start Cable locking systems Rack kit for 19 inch 4 post enclosures Two supports for tower position tower feet...

Page 11: ...e tower installation with the UPS To install the UPS Place the UPS on a flat stable surface in its final location Always keep 6 or 150 mm of free space behind the UPS rear panel for ventilation If ins...

Page 12: ...614 40096 00 12 Installation in rack position Follow steps 1 to 4 for module mounting on the rails The rails and necessary hardware are supplied by Eaton...

Page 13: ...4 EBM connection Tour installation A small amount of arcing may occur when connecting an EBM to the UPS This is normal and will not harm personnel Insert the EBM cable into the UPS battery connector q...

Page 14: ...rail on the front of the rack using the two holes at the bottom 3 Fix the ears plate to the UPS 4 Place the UPS on the rails and fix the ears plate to the top hole of the rail 5 Connect the EBM power...

Page 15: ...m being pulled out accidentally 3 To program shutdown and startup of the Group1 and Group2 outlets in order to extend battery runtime and perform scheduled shutdowns please see the In Out settings sec...

Page 16: ...on the HotSwap MBP module would cut supply to the equipment HotSwap MBP module operation The HotSwap MBP module has a rotary switch 45 with two positions Normal the load is supplied by the UPS LED 43...

Page 17: ...following table shows the indicator status and description Indicator Status Description Green On The UPS is On and the load is protected Yellow On The UPS is in battery mode and the load is protected...

Page 18: ...ormal mode LED indicator is illuminated Normal mode The UPS is operating normally The UPS is powering and protecting the equipment In AVR mode No beep The UPS is operating normally but the utility vol...

Page 19: ...ad segments Start battery test Starts a manual battery test possible if load 20 and battery 80 Change battery Disable charger Replace battery Update settings Connectivity test Dry contacts test Relay...

Page 20: ...enu Submenu Display information or Menu function Identification Type Model Part Number Serial Number UPS Firmware NMC Firmware IPV4 Address IPV6 Address Com card MAC Address Registration Links to Eato...

Page 21: ...disable the buzzer if an alarm occurs Enabled Level 0 8 6 Protected access Enabled Disabled Allow the user to lock the settings modification Password is 0577 Disabled In Out settings Output voltage 20...

Page 22: ...lt 90 min Enabled 90min Site Wiring Fault Enabled Disabled Prevents the UPS from starting if the phase and neutral wires are swapped Enebled Power Off alert Yes No If enabled activates a confirmation...

Page 23: ...y runtime at the expense of long term battery life warranty is also void if set to disable Enable Comm settings Input signals ROO RPO DB9 4 Sets Input signals parameters function delay operation throu...

Page 24: ...elay 0s 999s Restart Yes No For a proper server shutdown please make sure that the Output OFF delay is long enough Send CMD No Output OFF No OFF delay 0s Restart Yes On battery notice delay 0s 99s Set...

Page 25: ...and power managment of the UPS by adding a communication card compatible with the 5PXproduct Characteristics of the contact RS232 communication port Contact characteristics optocoupler Voltage 48 V D...

Page 26: ...connection and enables secure UPS monitoring over HTTPS web browser interface SNMP v1 v3 protocol and email alarms In addition up to 3 Environmental Monitoring Probes can be attached to obtain humidit...

Page 27: ...as RPO function and ROO terminal use as ROO function Remote Power Off RPO RPO is used to shutdown the UPS remotely when the contact is open This feature can be used for shutting down the load and the...

Page 28: ...described procedures Activate the external remote shut down contact to test the function Always test the RPO function before applying your critical load to avoid accidental load loss Programmable sign...

Page 29: ...tion 5 1 Start up and normal operation Check that the indications on the name plate located on the back of the UPS meets to the AC power source and the true electrical consumption of the total load Ba...

Page 30: ...ck the UPS status from the front panel to view the active alarms Correct the alarms and restart if necessary 5 3 UPS shutdown To shut down the UPS Press the button on the front panel for three seconds...

Page 31: ...uum cleaner For full battery life keep the equipment at an ambient temperature of 25 C 77 F The batteries are rated for a 3 5 year service life The length of service life varies depending on the frequ...

Page 32: ...l shock or burn from high short circuit current Observe the following precautions Remove watches rings or other metal objects Use tools with insulated handles Do not lay tools or metal parts on top of...

Page 33: ...r is needed to perform this procedure 1 Pull off the front panel by pressing the tabs on both sides 2 Disconnect the battery pack by separating the connectors never pull on the wires 3 Remove the meta...

Page 34: ...p MBP module goes OFF 6 6 Recycling the used equipment Contact your local recycling or hazardous waste center for information on proper disposal of the used equipment eaton com recycling Do not dispos...

Page 35: ...attery low Faults are announced by a continuous beep and red LED recorded into the Fault log and displayed on the LCD with a specific message box Example Out short circuit Use the following troublesho...

Page 36: ...f the condition persists contact your service representative The UPS does not provide the expected backup time The batteries need charging or service Apply utility power for 48 hours to charge the bat...

Page 37: ...vice Model number Serial number Firmware version number Date of failure or problem Symptoms of failure or problem Customer return address and contact information If repair is required you will be give...

Page 38: ...3000HRTNG2 Weights and dimensions Description UPS Weights lb kg Dimentions inch mm D x W x H 5PX1500HRTG2 49 4 22 4 17 6x17 2x3 4 448x438x85 5 5PX2200HRTG2 62 2 28 2 23 7x17 2x3 4 603x438x85 5 5PX3000...

Page 39: ...models Normal mode Battery mode Voltage regulation Boost Vin 1 15 Buck Vin 0 87 10 6 Efficiency 96 1000 2200 82 3000 85 Frequency regulation 0 1 Hz Nominal output 200 208 220 230 240V Frequency Follow...

Page 40: ...5PXEBM72RTG2 72Vdc 2 x 6 x 12V 9Ah 5PXEBM72RT3UAG2 72Vdc 2 x 6 x 12V 9Ah Type Sealed maintenance free valve regulated lead acid with minimum 3 5 year float service life at 25 C 77 F Monitoring Advance...

Page 41: ...mode 45 dB Batt Mode 45dB 50dB for 3K 9 Glossary AVR The Automatic Voltage Regulation maintains a constant voltage level for electrical equipment loads when the voltage falls outside the voltage toler...

Reviews: