672
02/16 MN05013001Z EN
Relay outputs
h
Caution!
Test the relay outputs at least once in 6 months.
ES4P-...-DR..., ES4P-...-DM...
Quantity
4 for ES4P-...-DR..
1 redundant for ES4P-…-DM…
Outputs in groups of
1
Parallel switching of outputs to
increase performance
Not permissible
Safety level in accordance with
EN 50156
3
redundant relay outputs,
6 months test interval
Protection of an output relay
Fuse: 6 A gL/gG, Circuit-breaker
with characteristic C: 24 V DC 4 A,
Short-circuit current IK < 250 A
Potential isolation
To power supply
yes
From the inputs
yes
From the PC interface, memory
card, NET network, EASY-Link
yes
Safe isolation according to EN 50178
V AC
300
Basic insulation
V AC
600
Lifespan, mechanical
Switch
opera-
tions
x
10
6
10
Contacts
Conventional thermal current
A
6
Rated impulse withstand
voltage
Ui
mp
contact coil
kV
6
Rated operational voltage
U
e
V AC
250