Output data: mode, R1 – R16
51
09/10 MN05013007Z-EN
Output data:
mode, R1 – R16
Attribute ID: 4
The cyclic data transfer between DeviceNet master and the
EASY222-DN slave is provided by the output data byte 0, 1
and 2.
Table 10:
Byte 0 to 2: output data, mode
The master writes the following data to the bytes 0, 1 and 2:
Table 11:
Byte 0: Operating mode
0 = status "0“ 1 = status "1"
Explanation:
Value 14
hex
= 00010100
bin
:
Byte 0 must always contain this value if data are to be
written to the easy/MFD basic unit via the EASY222-DN
gateway.
Value 34
hex
= 00110100
bin
:
This value sets the easy status from STOP to RUN. It is only
interpreted as command and therefore does not permit an
additional transfer of data. The index value 14
hex
must be
used in this situation.
Byte
Meaning
Value
0
Specifying the control mode
1
Setting/resetting of the easy/MFD
inputs R9 to R16
2
Setting/resetting of the easy/MFD
inputs R1 to R8
easy operating mode
Bit
7
6
5
4
3
2
1
0
Index for setting the basic unit to safety
state
0
0
0
0
0
0
0
0
Index for transferring valid data
0
0
0
1
0
1
0
0
RUN command
0
0
1
1
0
1
0
0
STOP command
0
1
0
0
0
1
0
0