Direct data exchange with
easy/MFD
(Polled I/O Connection)
54
09/10 MN05013007Z-EN
Table 13:
Byte 2: Setting/resetting of the easy/MFD inputs R1 to
R8
0 = status "0“ 1 = status "1"
Example:
Value 2B
hex
= 0010 1011
bin
:
Enables R6, R4, R2 and R1.
easy/MFD input
Bit
7
6
5
4
3
2
1
0
R1
0/1
R2
0/1
R3
0/1
R4
0/1
R5
0/1
R6
0/1
R7
0/1
R8
0/1
h
If control commands and I/O data are used at the same
time:
• The inputs will retain their previous state until this
control command has been executed.
• The input bytes will be updated after the data exchange
control command has been executed.