10 

4. Power cables connection 

Recommended protective devices and cable cross-sections 
Recommended upstream protection 

UPS power rating 

Upstream circuit breaker 

DX RT 6K UPS 

D curve – 63A 

DX RT 10K UPS 

D curve – 100A 

 
 
 
 
 
 

Read the Safety instructions page 3 regarding backfeed protection requirements. 
Recommended cable cross-sections 

Model 

DX RT 6K UPS 

DX RT 10K UPS 

Protective earthing conductor   
Min cross section 

6mm^2 (8AWG) 

10mm^2 (6AWG) 

Input L, N, G 
Min conductor cross section 

6mm^2 (8AWG) 

10mm^2(6AWG) 

Input fuse 

80A 

100A 

Output L,N, 
Min conductor cross section 

6mm^2 (8AWG) 

10mm^2(6AWG) 

It is recommended that an external isolating device should be installed between the 
mains input and UPS as shown in Figure   

 

 
 
 
 
 

 
AC Contactor: 208-240V, 63A (RT 6 kVA)208-240V, 100A (RT 10 kVA) 

 

 

N(L2)

 

To UPS Normal AC / Bypass AC source. 

G    N(L2) L1 

Summary of Contents for DX RT 6K UPS

Page 1: ...Eaton DX RT Online UPS 6000 10000VA XL IN USER MANUAL...

Page 2: ......

Page 3: ...00 4 8 Conducted magnetic field level 4 Performance IEC EN 62040 3 Special symbols The following are examples of symbols used on the UPS or accessories to alert you to important information RISK OF EL...

Page 4: ...ing Wear rubber gloves and boots Do not lay tools or metal parts on top of batteries Disconnect charging source prior to connecting or disconnecting battery terminals Determine if battery is inadverte...

Page 5: ...Special precautions The unit is heavy wear safety shoes and use vacuum lifter preferentially for handling operations All handling operations will require at least two people unpacking lifting install...

Page 6: ...packing the Unit 5 3 3 Checking the accessory kit 6 3 4 Install the unit 7 4 Power cables connection 10 4 1 Access to terminal blocks AC source to UPS 11 4 2 Access to terminal blocks PDU source to R...

Page 7: ...7 1Equipment care 35 7 2 Transporting the UPS 35 7 3 Storing the equipment 35 7 4 Replacing batteries 36 7 5 Recycling the used equipment 37 8 Troubleshooting 38 8 1 Typical alarms and faults 38 8 2 S...

Page 8: ...litate recycling separate the various packing components The cardboard we use comprises over 50 of recycled cardboard Sacks and bags are made of polyethylene Packing materials are recyclable and bear...

Page 9: ...be erratic These power problems have the potential to corrupt critical data destroy unsaved work sessions and damage hardware causing hours of lost productivity and expensive repairs With the UPS you...

Page 10: ...6 Parallel card optional 7 Dry IN OUT 8 Input Output terminal Standard model 5pole IPL IPN PE OPL OPN long backup model has 2 version one is 5 Pole Another is 7pole 7pole add bat bat and no external b...

Page 11: ...4 2 3 EBM Front panel 2 4 EBM rear panel RT EBM 13 Fuse board cover replace EBM fuse 14 EBM plug 15 EBM connector 2 3 Circuit diagram...

Page 12: ...s been damaged during shipment keep the shipping cartons and packing materials for the carrier or place of purchase and file a claim for shipping damage If you discover damage after acceptance file a...

Page 13: ...to facilitate sorting 3 3 Checking the accessory kit Verify that the following additional items are included with the unit Eaton DX RT UPS 6000VAIN 10000VAIN Eaton DX RT UPS 6000VAXLIN 10000VAXLIN DX...

Page 14: ...to be selected 1 Install Ear bracket to the unit by the M4 screws flat head 2 Slide the unit into rail kit and make sure tighten the rack mounting screw EBM model Identify the final position and keep...

Page 15: ...ction The battery number can be adjusted from 16pcs 1 strings to 20pcs 1 strings for this unit if you ordered other type EBM please contact with local sale center If installing additional unit place i...

Page 16: ...d install to Stabilizer bracket from UPS 2 Take the UPS EBM into Stabilizer bracket individually 3 Connect to UPS with Battery power cable Refer to rack position installing Note This unit is recommend...

Page 17: ...cable cross sections Model DX RT 6K UPS DX RT 10K UPS Protective earthing conductor Min cross section 6mm 2 8AWG 10mm 2 6AWG Input L N G Min conductor cross section 6mm 2 8AWG 10mm 2 6AWG Input fuse...

Page 18: ...qualified electrical personnel Before carrying out any connection check that the upstream protection devices Normal AC source and Bypass AC source are open O Off Always connect the ground wire first 1...

Page 19: ...he UPS s terminal blocks from PDU s source detail operation please refer to PDU s user manual 4 3 Parallel Installation and Operation Optional As long as the UPS is equipped with parallel board and pa...

Page 20: ...anical switch or static switch 2 Independent battery packs for each UPS 3 Remove the cover plate of parallel port on the UPS connect each UPS one by one with parallel cable and make sure the cable is...

Page 21: ...rs for the parallel UPS Pressing button continuously more than 1 second for one UPS of the system then the system will turn to line mode after these operations the system will work normally in paralle...

Page 22: ...l turn on after that the system will work in Line mode 3 How to remove a single UPS from parallel system 1 Firstly a main maintenance mechanical switch or static switch should be installed for the par...

Page 23: ...and the auto bypass setting is enable press the button to turn off the UPS system and the UPS system will turn to bypass mode 3 Transfer the main maintenance switch or static switch from UPS to BPS th...

Page 24: ...ettings The following table shows the indicator status and description Indicator Status Description Online model Green On The UPS is operating normally on Online or on High Efficiency mode Bat model O...

Page 25: ...100ms 1s to scroll down the menu option Enter next menu tree Press this button for 100ms 1s to select the present menu option or enter next menu but do not change any setting Select one menu option Pr...

Page 26: ...Beep every second Other Warning active Beep every second Battery output Beep every 4 seconds if battery low buzzer Beep every second Bypass output Beep every 2 minutes 5 2 LCD description The LCD back...

Page 27: ...ng the equipment with the battery power Prepare your equipment for shutdown High Efficiency mode The UPS is operating on High Efficiency mode Once the mains are loss or abnormal the UPS would transfer...

Page 28: ...will lose its protection 5 3 Display functions Use the two middle buttons and to scroll through the menu structure Press the Enter button to select an option Press the ESC button to cancel or return t...

Page 29: ...sh User password disabled Enabled disabled Audible alarm enabled disabled enabled Output voltage 208V 220V 230V 240V Can be changed in Standby mode and Bypass mode 230V Output frequency autosensing 50...

Page 30: ...after the UPS is turned on Take off all of the connected loads before turning off the UPS Starting the UPS with utility Verify that the total equipment ratings do not exceed the UPS capacity to preve...

Page 31: ...e UPS turns into Battery mode If the utility power comes back the UPS will transfer to Line mode without output interruption of the UPS UPS shutdown with utility To shut down the UPS with utility Pres...

Page 32: ...the user own requirements optimize the function of UPS The main menu In the default UPS status summary screen when pressing or 300ms the detailed information about alarm battery the system status wou...

Page 33: ...on the menu of UPS status the display would enter the next UPS status menu tree The content of UPS status menu tree is same as the default UPS status summary menu By pressing ESC 300ms the display wo...

Page 34: ...d enter the next measurement menu tree A lot of detailed useful information could be checked here Ex the output voltage and frequency the output current the load capacity the input voltage and frequen...

Page 35: ...ayed one by one The max number of record is 100 when the number is larger than 100 the latest will replace the previous By pressing ESC 300ms the display would return the last main menu tree The contr...

Page 36: ...pass mode And the reason of fault should be checked and deleted before UPS is turned on again by manual operation Restore factory settings all the settings would be recover to default factory settings...

Page 37: ...ing menu Please contact your local distributor for further information before using the settings Some settings would be changed the specification and some settings would enable or disable some functio...

Page 38: ...31...

Page 39: ...V By press 1s The option would flash Output voltage 230V By press 1s Setting menu tree Output voltage 220V By press or 100ms to select the wanted option Output voltage 220V By press 1s to confirm the...

Page 40: ...ction When the EPO function is enabled default setting once the EPO port is pulled out the UPS would shut off the output and enter into EPO mode and the UPS would not respond anything ON OFF request u...

Page 41: ...n 2 MODBUS card provides connection to Modbus protocol with standard RS485 signal To see more detail please check the MODBUS user manual 3 This series UPS has AS400 card an optional accessory for AS40...

Page 42: ...erature of 25 C 77 F If the UPS requires any type of transportation verify that the UPS is disconnected and turned off The batteries are rated for a 3 5 year service life The length of service life va...

Page 43: ...er new batteries Proper disposal of batteries is required Refer to your local codes for disposal requirements Never dispose of batteries in a fire Batteries may explode when exposed to flame Do not op...

Page 44: ...cable s into the battery connector s 4 Verify that the EBM connections are tight and there are adequate bend radius and strain relief exist for each cable Testing new batteries 1 Charge the batteries...

Page 45: ...intended to alert the user Events are silent status information that are recorded into the Event log Example Battery charging Alarms are recorded into the Event log and displayed on the LCD status scr...

Page 46: ...er Fault code A503 Fault light flashes 1 beep every 1 second UPS charger fault Output voltage is too low Please contact your supplier Fault code F613 Fault lamp lights long Beep continuous Indicates t...

Page 47: ...t lamp lights long Beep continuous Indicates that the UPS has detected abnormally low impedance placed on its output and considers it a short circuit Remove all the loads Turn off the UPS Check if UPS...

Page 48: ...UPS has cut off the output and transferred to fault mode because of overload in bypass mode Remove some of the equipment from the UPS Fault code A900 Fault LED is flash 1 beep every 1 second An overlo...

Page 49: ...cable connect OK Fault code A012 AC18 Fault LED is flash 1 beep every 1 second Parallel system UPS1 line ok UPS2 line loss Check the line input Fault code A00F AC19 Fault LED is flash 1 beep every 1 s...

Page 50: ...dc 7Ah 6000 10000VA Eaton DXRT EBM 192 09 RT3U IN RT 192Vdc 9Ah 6000 10000VA Table 3 Weights and dimensions Description Weights kg Dimensions mm W x H x D Eaton DX RT 6000VAIN 13 3 438 86 3 573 Eaton...

Page 51: ...RT 10000VAXLIN Table 6 Electrical output All models Normal mode Battery mode Voltage regulation 1 1 Efficiency 98 High Efficiency mode 95 93 Frequency regulation 50Hz 0 1Hz 50Hz 0 1Hz Nominal output 2...

Page 52: ...EN 62040 2 Cat C3 IEC EN 62040 3 EN 60950 1 EMC Emissions Conduction C3 IEC EN 62040 2 Radiation C3 IEC EN 62040 2 EMC Immunity IEC 61000 4 2 Level 3 IEC 61000 4 3 Level 3 IEC 61000 4 4 Level 4 also o...

Page 53: ...ar float service life at 25 C 77 F Lifetime is reduced above 30 C Monitoring Advanced monitoring for earlier failure detection and warning Battery port External ANEN SA30 connector on power module for...

Page 54: ...r Load Devices or equipment connected to the UPS output HE mode Operating mode by which the load is supplied directly by the AC source if it is within the tolerances defined by the user This mode redu...

Page 55: ...48...

Page 56: ...49 614 02180XT1...

Reviews: