Core Power Solutions (DV2-C16 Models)
56
Copyright © 2008-2009 Eaton Corporation. All Rights Reserved.
IPN 997-00012-71B July 2009
CB Rating
(Note 1)
Cable Size
AWG
(Note 2)
2-hole Crimp Lug(s)
(Note 3)
Crimping Tool
(Note 3)
100A
1
YAV1CL-2TC38-FX
Y1MRTC
225A
4/0
YAV28L-2TC38-FX
400A
2 x 4/0
2 x YAV28L-2TC38-FX
700A
2 x 500 kcmil
2 x YA38L-2NT38-FX
1000A
3 x 400 kcmil
3 x YA36L-2NT38-FX
M29-11
Notes:
1
See circuit breaker part numbers and derating factors on page
2
Minimum cable size. Does not allow for excessive voltage drop in long cable runs at high
current.
3
Part numbers are for FCI-BURNDY® products. In US/Canada use these parts or
equivalent UL-listed crimp lugs.
Step 4 - Connect cables
1
Connect the live (negative) cables to the circuit breaker terminals.
2
Connect the common (positive) cables to the common bar.
Step 5 - Check terminations, secure cables and test insulation
1
Check all circuit breaker terminations are correct and tighten to 18.7 -
21.9Nm (166 - 194 inch-pounds).
2
Secure the cables with cable ties to ensure there will be no strain on the
terminals.
3
Test the insulation resistance of the cables.
Step 6 - Refit panels and circuit breaker cover
1
Refit the cabinet panels.
2
Refit the circuit breaker cover.
Fit blank covers over any unused circuit breaker positions.
Step 7 - Switch on circuit breaker(s) (if required)
1
Refer to the equipment manufacturer's instructions before applying dc
power to any equipment.
2
To apply dc power to the equipment, switch on the circuit breaker.
3
Close the hinged front cover.
Procedure complete