![Eaton DV2-C16-3 Series Installation And Operation Manual Download Page 10](http://html1.mh-extra.com/html/eaton/dv2-c16-3-series/dv2-c16-3-series_installation-and-operation-manual_3839492010.webp)
Core Power Solutions (DV2-C16 Models)
4
Copyright © 2008-2009 Eaton Corporation. All Rights Reserved.
IPN 997-00012-71B July 2009
Alarm notifications may be by SNMP traps, SMS text messaging, dial-out to PowerManagerII
remote monitoring software, or relay contact closures.
"
Power on LED (green)
#
Minor alarm LED (yellow)
$
Critical/Major alarm LED
(red)
%
Color LCD display
!
Soft keys (2)
&
Navigation keys (4)
3
USB 1.1 connector (12Mb/s)
4
Retaining screw
5
Power and system
communications connector
'
RS232 connector
(
Ethernet connector and
status LEDs
The SC200 is supplied pre-configured with either a default configuration file, or with one
factory customized for a particular application. Some configuration file changes can be made
with the keypad, or all settings can be changed via a PC connected to the USB interface. For
details refer to the SC200 Operation Handbook (see Related Information on page
).
See Troubleshooting on page
for details of SC200 alarms. For connector pin-outs refer to
the SC200 Operation Handbook (see Related Information on page
Compatible Software
The following software is compatible with the SC200 system controller:
•
DCTools Configuration Software. Latest version is available free from
www.powerquality.eaton.com/downloads.
•
PowerManagerII Remote Control and Monitoring Software. Contact your Eaton dc
product supplier for further information (see Worldwide Support on page
•
Recommended web browsers: Microsoft Internet Explorer 8 (IE6 is compatible but with
reduced performance), Mozilla Firefox 3.0.
Input/Output Board
The input/output (I/O) board provides the I/O interfaces and connections for the SC200
system controller.
The I/O board includes a range of sense inputs for dc power system control and monitoring.
It also allows real time data collection from building services and other external devices, and