background image

Current Path Resistance Test

Purpose

To measure and record the dc electrical resistance of 

the main current carrying pole unit assembly in the 

VR-Series power circuit breaker. This measurement is 

performed by injecting 100A dc from terminal to terminal 

of each pole unit in the closed position and measuring 

the voltage drop across the terminals. The resistance 

can be calculated from Ohm’s Law and is expressed in 

micro-ohms.

The main contacts are inside the vacuum chamber, 

which remain clean and require no maintenance at 

any time. The VR-Series design does not have sliding 

contacts at the moving stem and use a highly reliable 

and unique flexible clamp design that eliminates the 

need for lubrication and inspection for wear.

This test may be performed during regular maintenance 

intervals and the results should not exceed the factory 

recorded values by 15% when adjusted to the same 

temperature recorded during the factory tests.

Equipment

This test should be performed with a low voltage, 

direct current (dc) power supply capable of delivering 

no less 100A dc. The factory performs this test using a 

Digital Low Resistance Ohmmeter (DLRO). The DLRO 

injects 100A dc, measures the voltage drop across the 

terminals and displays the resistance in micro-ohms.

Procedure

The current path resistance test is to be performed per 

ANSI/IEEE C37.09-1999 section 5.5.

Test

Perform the test as follows (Using the DLRO) 

1.  Remove the circuit breaker from its enclosure if 

installed (follow the removal procedures) and move it 

to a suitable area away from the Arc-Flash boundary.

2.  Remove the finger clusters from the terminals being 

tested.

3.  Manually or electrically charge the circuit breaker. 
4.  Manually or electrically close the circuit breaker. If 

the circuit breaker is being closed electrically, the 

charging motor will run if control power is present 

after the circuit breaker is closed.

5.  Provide control power to the DLRO and turn it to the 

ON position. Select 100A output, if adjustable.

6.  Connect the DLRO positive current lead to the TOP 

terminal of the phase being tested.

7.  Connect the DLRO negative current lead to the 

BOTTOM terminal of the phase being tested.

8.  Press the TEST button on the DLRO. Once the 

TEST button is pressed, 100A dc will flow through 

the phase being tested. If the circuit breaker is not 

closed, the DLRO will not inject current.

9.  Apply the DLRO positive measurement test lead 

to the TOP terminal. Be mindful not to connect this 

measurement lead to the current lead. This insures 

that the current lead is not being calculated into the 

resistance of the current path.

10. Apply the DLRO negative measurement test lead to 

the BOTTOM terminal. Be mindful not to connect this 

measurement lead to the current lead. This insures 

that the current lead is not being calculated into the 

resistance of the current path.

11. While both measurement leads are connected, 

observe the resistance reading and record the value.

12. Press the TEST button on the DLRO to stop the 

current flow.

13. Remove the measurement leads and current leads 

from the phase being tested.

14. Install the finger clusters back onto the terminals of 

the circuit breaker.

15. Repeat above procedure for the remain phases of the 

circuit breaker.

16. Open the circuit breaker after completion of the 

testing.

17. Turn the DLRO to the OFF position and remove 

control power if necessary.

18. Re-insert the circuit breaker into the enclosure per 

insertion procedures.

Results

The field measured resistance should not exceed the 

factory values no more than 15%. If measurements 

exceed 15%, check the primary current path for loose 

hardware and re-torque per the VR-Series instruction 

booklet. Repeat the test if any loose hardware and 

re-torqueing is applied. If the values do not improve, 

contact the manufacturer.

Resistance conversion for Temperature
R

conversion 

= R

Factory  

( 1 + (  T

Field

 - T

Factory  

r

)

R

conversion 

= Resistance correction for temperature based from the factory 

resistance measurement.

R

Factory 

= Resistance measurement from the factory.

T

Field 

= Temperature measurement in the field.

T

Factory 

= Temperature measurement from the factory.

r

 = Copper resistivity temperature coefficient.

r

 = 0.002167 Copper Resistivity Temperature Coefficient / Deg F

r

 = 0.0039 Copper Resistivity Temperature Coefficient / Deg C

Resistance Converter (

In Degrees Fahrenheit

):

R

conversion Field 

=

 

F

R

Factory 

:

T

Factory

:

T

Field 

:

6

EATON

   |   Visual Instruction Booklet Essentials   |   DST-2-VR - 18WR Element   |   May 2017  

0.000

Summary of Contents for DST-2-VR

Page 1: ...For VR Series Circuit Breakers This is a user interactive supplemental booklet This material is intended to enhance the technical information included in the instruction booklet for the vacuum replace...

Page 2: ...on and maintenance of medium voltage circuits and equipment should be permitted to work on these circuit breakers Always remove the circuit breaker from the enclosure before performing any maintenance...

Page 3: ...m Interrupter Assembly Each interrupter is assembled at the factory as a unit to assure correct dimensional relationships between working components The interrupter assembly consists of a vacuum inter...

Page 4: ...ENTIAL TESTS ARE NOT RECOMMENDED BY EATON DO NOT APPLY DC AT ANY LEVEL TO VR SERIES POWER CIRCUIT BREAKERS With the circuit breaker open and securely sitting on the floor connect all top front primary...

Page 5: ...L BELOW MAXIMUM PERMITTED BY STANDARDS HOWEVER AS A PRECAUTIONARY MEASURE AGAINST POSSIBILITY OF APPLICATION OF HIGHER THAN RECOMMENDED VOLTAGE AND OR BELOW NORMAL CONTACT SPACING IT IS RECOMMENDED TH...

Page 6: ...BOTTOM terminal of the phase being tested 8 Press the TEST button on the DLRO Once the TEST button is pressed 100A dc will flow through the phase being tested If the circuit breaker is not closed the...

Page 7: ...ent speed for interruption Stroke is the gap between fixed and moving contacts of a vacuum interrupter with the circuit breaker open The circuit breaker mechanism provides a fixed amount of motion to...

Page 8: ...d the motor eccentric These bearings are packed at the factory with a top grade slow oxidizing grease which normally should be effective for many years They should not be disturbed unless there is def...

Page 9: ...bracket and tighten Do not over tighten Fish wires through to terminal block Connect wires to terminal block TB1 and TB2 Install tie wraps to hold wire bundle Mechanically and electrically test the c...

Page 10: ...k the threads Remove the two screws on the right hand motor support plate using a 9 64in Allen wrench Remove the motor plate from the side sheet for the 5kV circuit breaker Remove the motor Verify the...

Page 11: ...afety Precautions Read and understand the instruction manual for specific instructions before attempting any maintenance repair or testing on the circuit breaker The user is cautioned to observe all r...

Page 12: ...VR Series Circuit Breaker DST 2 5 VR 350 2000A 12 EATON Visual Instruction Booklet Essentials DST 2 VR 18WR Element May 2017...

Page 13: ...VR Series Circuit Breaker DST 2 15 VR 1200A 13 EATON Visual Instruction Booklet Essentials DST 2 VR 18WR Element May 2017...

Page 14: ...nts and engineering services Eaton is positioned through its global solutions to answer today s most critical electrical power management challenges Eaton is a power management company with 2015 sales...

Reviews: