3 Installation
3.3 Flush mounting in control panel
DS7 Soft starter
09/16 MN03901001Z-EN
www.eaton.com
63
3.3.1 Increased cooling
Cooling air circulation on the DS7 soft starter can be improved by using an
optional DS7-FAN-… device fan
This makes the following possible:
•
Operation at higher ambient air temperatures
•
A compact setup and directly combining the unit with other components
•
A higher number of starts per hour
The choice of device fan is based on the rated operational current (yyy) for
the corresponding size.
Table 11: Device fans for the various rated operational currents
→
The supplied cooling air must have a temperature between
-5 and +40 °C. A derating is required for higher temperatures
(up to +60 .maximum):
•
2 percent of the rated operational current I
e
per Kelvin (K)
temperature rise from +40 °C
•
1 percent of rated operational current I
e
per kelvin (K) of
temperature rise after +40 °C with device fan (DS7-FAN-…)
→
DS7-FAN-… device fans are temperature-controlled, always run
during ramp times (t-Start, t-Stop), and will continue running
until the heat sink cools down again. The fan is then
automatically switched off.
→
It is advisable to install device fan DS7-FAN-… before installing
soft starter DS7 in the basic device.
This helps prevent additional steps for removal and changes in
the installation.
DANGER
The device fan must only be mounted in a de-energized state.
Rated operational current (yyy)
Construction
size
Device fan (type)
Arrangement
004 - 012
BG1
DS7-FAN-032
Flush mounting
016 - 032
BG2
DS7-FAN-032
Flush mounting
041 - 100
BG3
DS7-FAN-100
Substructure
135 - 200
BG4
DS7-FAN-200
Substructure
→
For technical data for DS7-FAN… device fans, refer to
Summary of Contents for DS7 Series
Page 1: ...Manual DS7 Soft starter 09 16 MN03901001Z EN...
Page 4: ...II...
Page 36: ...1 Device series DS7 1 14 Function 32 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 96: ...3 Installation 3 6 Insulation test 92 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 188: ...8 SmartWire DT 8 9 Programming 184 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...