EMEA Fire Technical Support: DF6000/CF3000 Applications Guide
Daylight Saving
Fig 35
Daylight saving mode which would normally be set for the UK market can now be disabled in the high-
level menu.
BS 5839 Button
This button has been added for when there is significant cause and effect programmed into the
system, but the outputs need to meet BS5839 specification.
Fig 36
This means that when selected and a Callpoint is activated, the sounders will operate within the 3
seconds required by BS overriding any sounder cause and effect. However, the remaining cause and
effect for output devices will only follow when the time to process this is available.
Global Weekly Walk tests
If the panel is part of a Network, the customer may require the weekly and walk tests to be transmitted
across the network
– which is defaulted to activate the local panel only, choose this button on all
panels in the Network, the test can then be initiated from any panel..