Appendix D: Assembly Object Instances for MP-4000
Produced Assembly Instances
There are 11 producing assemblies supported for the MP-4000, as indicated in the following table.
Table D-1. Assembly Object Instances.
Inst #
Assembly Name
Number of
Data Bytes
Access
150
Status 4
Get
151
Temperatures
26
Get
152
Currents 14
Get
153
MotorData
20
Get
154
MotorMaximums 58 Get
155
MotorTripCounts
68
Get
156
MotorAlarmCounts 40
Get
157
Flags
18
Get
158
Voltages 22
Get
159
Power
62
Get
160
Energy 30
Get
161
Reserved
-
Get
162
Reserved -
Get
163
Reserved
-
Get
164
Reserved -
Get
Table D-2. Format of Assembly Instance # 150(96h) – Status.
Word #
Member
Parameter
Inst #
Data Bytes
0
Status
32
2
1
StatusByte
33
2
Table D-3. Format of Assembly Instance # 151(97h) – Temperatures.
Word #
Member
Parameter
Inst #
Data Bytes
0
Status 32
2
1
StatusByte
33
2
2
WindingTemp1 40 2
3
WindingTemp2
41
2
4
WindingTemp3 42 2
5
WindingTemp4
43
2
6
WindingTemp5 44 2
7
WindingTemp6
45
2
8
MotorBrngTemp1 46 2
9
MotorBrngTemp2
47
2
10
LoadBrngTemp1 48 2
11
LoadBrngTemp2
49
2
12
AuxiliaryTemp 50 2
Table D-4. Format of Assembly Instance #152 (98h) – Currents.
Word #
Member
Parameter
Inst #
Data Bytes
0
Status 32
2
1
StatusByte
33
2
2
CurrentPhA 51 2
3
CurrentPhB
52
2
4
CurrentPhC 53
2
5
CurrentGnd
54
2
6
CurrentAvg3Ph 55 2