Step 5: Apply Utility (Normal) Power. If the switch is
properly applied for the system voltage ordered, the dis-
play should work and the
Normal Source (Source 1)
Available LED should light (Figure 6). Using a voltmeter,
check for proper system voltage on the normal and load
terminals. Check all phases on a three-phase switch.
Voltage measurements should be taken phase to phase
and phase to neutral.
Figure 6 IQ Transfer Logic (Utility Supplying Load)
●
●
●
●
The following lights must be ON:
●
Source 1 Available
●
Source 1 Preferred
●
Source 1 Connected
●
Load Energized
Perform LED lamp test by depressing
and holding. All LED’s should turn on.
If not, contact factory for replacement.