I.L. 29C211E

Effective 04/04

in the OFF position. The switch is held closed when the
cover is in place and the padlock bracket is in the non-
padlockable position.

2-0  INSTALLATION

The electrical operator is normally supplied as a sepa-
rate item for mounting on an uninstalled circuit breaker.
If an electrical operator is to be mounted on an installed
circuit breaker, all power must be removed from the cir-
cuit breaker before proceeding to mount the electrical
operator.

The installation procedure consists of inspecting and
mounting the electrical operator and connecting control
wiring. To install the electrical operator, perform the fol-
lowing steps:

BEFORE MOUNTING AN ELECTRICAL OPERATOR
ON A CIRCUIT BREAKER INSTALLED IN AN ELEC-
TRICAL SYSTEM, MAKE SURE THE CIRCUIT
BREAKER IS SWITCHED TO THE OFF POSITION
AND THAT THERE IS NO VOLTAGE PRESENT

Figure 1-3  Circuit Breaker Handle in CLOSED Position

Armature
Drive
Plate

Molded 
Trigger

Magnet
Coil
Assembly

Logic
Control
Cutoff
Switch

Magnet
Drive
Plate

Bi-stable
Latch

Magnet 
Coil
Assembly

Circuit Breaker
Handle 
(CLOSED Position)

!

WARNING

Figure 1-4  Electrical Operator Connection and Schematic Diagram

Logic Control
Cutoff Switch

PB1

PB2

M1

M2

COM

OFF

ON

(-)

COIL

GND

F1

F1

C1

C2

S1

(+)

COIL

S2

Solenoid 
Coil

Solenoid 
Coil

Cover Lockoff

F1 Fuse (Supplied by Customer)
PB1, 2 Pushbutton (Supplied by Customer)
C1/M1 Operating Contactor
C2/M2 (Supplied by Customer)

➀ 

Electrical Rating 10A at 125 Vac, 5A at 250 Vac

Page 3

Summary of Contents for Cutler-Hammer J-Frame Series

Page 1: ...mation The electrical operator Figure 1 1 is a dual solenoid mechanism for local and remote circuit breaker ON and OFF reset switching The electrical operator is mount ed on the cover of the circuit b...

Page 2: ...it breaker handle moves the cutoff switch disconnects power to the external coil switch and the bistable latch toggles so that the latch blocks the magnets the next time the solenoids are energized Th...

Page 3: ...rm the fol lowing steps BEFORE MOUNTING AN ELECTRICAL OPERATOR ON A CIRCUIT BREAKER INSTALLED IN AN ELEC TRICAL SYSTEM MAKE SURE THE CIRCUIT BREAKER IS SWITCHED TO THE OFF POSITION AND THAT THERE IS N...

Page 4: ...new circuit breaker using special stacking screws provided with the electrical operator Figure 2 1 Tighten screws firmly but do not exceed 28 pound inches 8 N m When the electrical operator is mounted...

Page 5: ...wn in Figure 2 2 and Table 2 1 into the load end by lifting the solenoid operator up enough to start the screws in the top of the special threaded stacking screws Imperial 1 Screw stacking special Imp...

Page 6: ...erator frame The ground connect a ground conductor green as shown in Figure When the assembly is mounted on an insulated surface See Figure 1 4 2 10 Connect control wires to remote control devices TB1...

Page 7: ...OPERATING RATE OF ONE OPERATION PER MINUTE FAILURE TO OBSERVE THIS OPERATING RATE CAN RESULT IN DAMAGE TO THE ELECTRICAL OPERATOR 3 1 Slide REMOTE OPERATION switch to the ON position by moving padloc...

Page 8: ...to verify adequate voltage and power capability to operator Check to insure proper breaker handle operator engagement and secure mounting Refer to electrical and mounting sections of the instructions...

Page 9: ...I L 29C211E Fig 5 1 Electrical Solenoid Operator Mounted on 3 Pole K Frame Breaker Page 9 Effective 04 04...

Page 10: ...I L 29C211E Fig 5 2 Electrical Solenoid Opertor Mounted on 3 Pole J Frame Breaker Effective 04 04 Page 10...

Page 11: ...I L 29C211E Effective 04 04 Page 11 NOTES...

Page 12: ...I L 29C211E Pittsburgh Pennsylvania U S A Effective 04 04 Style 6631C42H06 Printed in U S A TQC NOTES...

Reviews: