I.L. 29C211E

Effective April 2004  Supersedes I.L. 29C211D dated October 2002

Instructions for Installation of 120 and 240 Vdc Electrical
(Solenoid) Operator on J

-Frame and K-Frame Series C Circuit 

Breakers and Molded Case Switches 

DO NOT ATTEMPT TO INSTALL OR PERFORM MAIN-
TENANCE ON EQUIPMENT WHILE IT IS ENERGIZED.
DEATH, SEVERE PERSONAL INJURY, OR SUBSTAN-
TIAL PROPERTY DAMAGE CAN RESULT FROM CON-
TACT WITH ENERGIZED EQUIPMENT. ALWAYS VER-
IFY THAT NO VOLTAGE IS PRESENT BEFORE PRO-
CEEDING WITH TASK, AND ALWAYS FOLLOW GEN-
ERALLY ACCEPTED SAFETY PROCEDURES.

CUTLER-HAMMER IS NOT LIABLE FOR THE MISAP-
PLICATION OR MISINSTALLATION OF ITS PRODUCTS.

The user is cautioned to observe all recommendations,
warnings, and cautions relating to the safety of person-
nel and equipment, as well as, all general and local
health and safety laws, codes and procedures.

The recommendations and information contained herein
are based on Cutler-Hammer experience and judge-
ment, but should not be considered to be all-inclusive or
covering every application or circumstance which may
arise. If any questions arise, contact Cutler-Hammer for
further information or instructions.

1-0  INTRODUCTION

General Information

The electrical operator (Figure 1-1) is a dual-solenoid
mechanism for local and remote circuit breaker ON and
OFF (reset) switching. The electrical operator is mount-
ed on the cover of the circuit breaker and provides high
speed switching with operating times of less than 5
cycles (80 ms), making it suitable for small generator
synchronizing operations. The electrical operator has a
terminal block for control connections. Catalog numbers
and electrical rating data are shown in Table 1.1. The
electrical operator is Underwriters Laboratories, Inc.
Iisted as a circuit breaker accessory suitable for field
installation under UL File E64983

.

The electrical operator is suitable for application with 3
and 4-pole Series C circuit breaker types J

-Frame and

K

-Frame. 

UL listing pending.

!

WARNING

Figure 1-1  Electrical (Solenoid) Operator Installed on K-
Frame Circuit Breaker

Catalog Voltage

Inrush

Fuse

Numbers

(V)

Current

(A)

(A) DC

J-Frame
EOP2T07DC            120                      31                     10
EOP2T

11DC            240                      20                       5

Table 1.1  Electrical (Solenoid) Operator Catalog Numbers
Electrical Rating Data 

➀➁➂➃➅ 

(See Figure 1-4 for

Additional Data)

Frequency: DC

Maximum operating time: 5cycles (80ms)

Maximum rate of operation: 4 operations per minute

Tolerance: ±10% of nominal voltage.  Short lead 

length from DC power supply recommended

Maximum coil on time: 5 seconds

Power supply to be one KVA minimum

K-Frame

EOP3MT07DC          120                      31                     10
EOP3MT11DC          240                      20                       5

Summary of Contents for Cutler-Hammer J-Frame Series

Page 1: ...mation The electrical operator Figure 1 1 is a dual solenoid mechanism for local and remote circuit breaker ON and OFF reset switching The electrical operator is mount ed on the cover of the circuit b...

Page 2: ...it breaker handle moves the cutoff switch disconnects power to the external coil switch and the bistable latch toggles so that the latch blocks the magnets the next time the solenoids are energized Th...

Page 3: ...rm the fol lowing steps BEFORE MOUNTING AN ELECTRICAL OPERATOR ON A CIRCUIT BREAKER INSTALLED IN AN ELEC TRICAL SYSTEM MAKE SURE THE CIRCUIT BREAKER IS SWITCHED TO THE OFF POSITION AND THAT THERE IS N...

Page 4: ...new circuit breaker using special stacking screws provided with the electrical operator Figure 2 1 Tighten screws firmly but do not exceed 28 pound inches 8 N m When the electrical operator is mounted...

Page 5: ...wn in Figure 2 2 and Table 2 1 into the load end by lifting the solenoid operator up enough to start the screws in the top of the special threaded stacking screws Imperial 1 Screw stacking special Imp...

Page 6: ...erator frame The ground connect a ground conductor green as shown in Figure When the assembly is mounted on an insulated surface See Figure 1 4 2 10 Connect control wires to remote control devices TB1...

Page 7: ...OPERATING RATE OF ONE OPERATION PER MINUTE FAILURE TO OBSERVE THIS OPERATING RATE CAN RESULT IN DAMAGE TO THE ELECTRICAL OPERATOR 3 1 Slide REMOTE OPERATION switch to the ON position by moving padloc...

Page 8: ...to verify adequate voltage and power capability to operator Check to insure proper breaker handle operator engagement and secure mounting Refer to electrical and mounting sections of the instructions...

Page 9: ...I L 29C211E Fig 5 1 Electrical Solenoid Operator Mounted on 3 Pole K Frame Breaker Page 9 Effective 04 04...

Page 10: ...I L 29C211E Fig 5 2 Electrical Solenoid Opertor Mounted on 3 Pole J Frame Breaker Effective 04 04 Page 10...

Page 11: ...I L 29C211E Effective 04 04 Page 11 NOTES...

Page 12: ...I L 29C211E Pittsburgh Pennsylvania U S A Effective 04 04 Style 6631C42H06 Printed in U S A TQC NOTES...

Reviews: