Control wiring
A minimum of 16 AWG should be used between the power supply
and the 24 Vdc + and – terminals.
Terminal connections are to be secured to a torque value of 3.6 lb-in.
Control wiring is connected to the DS6 soft start controller by a
9-pin terminal block located on the front of the unit. Use the wiring
diagrams in
Figure 4
,
Figure 5
, and the information in
Table 7
as guides.
Figure 4. Direct Start
Table 6. Terminal Designations
Terminal
Description
OV
Control ground or power supply common
+24
Plus 24 Vdc from power supply
–A2
Common with 0V, connected externally
EN
Start command enable/stop command
+A1
Start command/ramp stop command
13, 14
Top of ramp contacts—NO
23, 24
Ready status contacts—NO
0V +24
TOR
Ready
–A2 EN +A1 13
14
24
+24V
0V
23
0V +24 –A2 EN +A1 13 14
24
23
Q1
Control Wiring Terminal Block
Figure 5. Direct Start With Soft Stop
Table 7. DS6 Terminal Control Block Wiring
Name
Block
Designation
Input
Connections
Circuit
common
0V
Common
Common
Power
+24
24 Vdc nominal (see 24 Vdc power
supply requirements) section for
sizing of power supply
+24 Vdc power from
power supply
–A2
–A2
Control power common
Common
Enable
EN
24 Vdc maintained
START command with
+A1 energized. Remove
for STOP command
+A1
+A1
24 Vdc maintained
START command
with EN energized.
Remove for STOP
RAMP command
Relay
13
NO contact rated @ 250 Vac,
3A resistive, 1A inductive
Top of ramp signal–
in bypass
14
NO contact rated @ 250 Vac,
3A resistive, 1A inductive
Top of ramp signal–
in bypass
Relay
23
NO contact rated @ 250 Vac,
3A resistive, 1A inductive
READY status signal
24
NO contact rated @ 250 Vac,
3A resistive, 1A inductive
READY status signal
0V +24
TOR
Ready
-A2 EN +A1 13 14
24
+24V
0V
23
Q1
S3