Instructional Leafl et 

IL03901001E

Effective June 2009

DS6 series soft start controllers 
  
  

EATON CORPORATION

 www.eaton.com

Power wiring

Using the wiring diagrams in 

Figure 3

,

 Figure 4, 

and 

Table 3 

as 

guides, connect the line, motor, and power supply wiring in 
accordance with appropriate local and national codes. 

ote: 

N

To provide optimum motor protection, the line and motor power wiring 

should be tightly bundled and run perpendicular to the orientation of the DS6.
Soft start controller to motor cable length is not to exceed 325 ft (100m).

Figure 3.  Power Wiring Diagram for 230/400 and 400/460V 
Line Voltages

1

3

5

L1

L2

L3

2

4

6

T1

T2

T3

M

3~

DS6

Table 3.   Power Wire Sizing and Torque Requirements 

Frame Size

Wire Size

Torque

Wire Strip Length

25–75 hp

12–8 AWG

53 lb-in

0.65 in

25–75 hp

6–2/0 AWG

80 lb-in

0.65 in

100–150 hp

12–8 AWG

44 lb-in

0.87 in

100–150 hp

6 AWG—350 kcmil

123 lb-in

0.87 in

 DANGER 

HAZARDOUS VOLTAGE. WILL CAUSE DEATH OR SERIOUS INJURY. 
HAZARDOUS VOLTAGE IS PRESENT IN THE OFF/STOP STATUS OF THE SOFT 
START CONTROLLER WHEN THE LINE VOLTAGE IS ENERGIZED.

Table 4.  Product Selection—Horsepower Ratings

Catalog Number

Rated 
Current
(A)

Motor Power

Maximum Allowable 
Breaker Size 

Maximum Allowable 
Fuse Size 

200V

230V

460V

(hp)

(hp)

(hp)

DS6-34DSX041N0-N

40

10

10

30

HFD3150L

150A Class RK5

DS6-34DSX055N0-N

52

15

20

40

HFD3200L

200A Class RK5

DS6-34DSX068N0-N

65

20

25

50

HJD3250

200A Class RK5

DS6-34DSX081N0-N

77

25

30

60

HKD3300

300A Class RK5

DS6-34DSX099N0-N

96

30

30

75

HKD3350

350A Class RK5

DS6-34DSX134N0-N

124

40

50

100

HKD3350

500A Class RK5

DS6-34DSX161N0-N

156

50

60

125

HLD3450

500A Class RK5

DS6-34DSX196N0-N

180

60

75

150

HLD3500

500A Class RK5

 

Maximum values are higher than allowed per NEC

 430.52 and UL 508A 31.1.

Table 5.  Product Selection—kW Ratings According to IEC 60947-4-2

Catalog Number

Rated 
Current
(A)

Motor Power

Maximum Allowable 
Breaker Size 

Maximum Allowable 
Fuse Size 

230V

400V

(kW)

(kW)

DS6-34DSX041N0-N

41

11

22

HFD3150L

150A Class RK5

DS6-34DSX055N0-N

55

15

30

HFD3200L

200A Class RK5

DS6-34DSX068N0-N

68

15

37

HJD3250

200A Class RK5

DS6-34DSX081N0-N

81

22

45

HKD3300

300A Class RK5

DS6-34DSX099N0-N

99

30

55

HKD3350

350A Class RK5

DS6-34DSX134N0-N

134

30

75

HKD3350

500A Class RK5

DS6-34DSX161N0-N

161

45

90

HLD3450

500A Class RK5

DS6-34DSX196N0-N

196

55

110

HLD3500

500A Class RK5

 

Maximum values are higher than allowed per NEC 430.52 and UL 508A 31.1.

Considerations:

1. Either XTOB, C306, or C396 series or equivalent overload protection devices may be selected.

2. Isolation contactor is optional for normal applications. It is recommended for mains isolation.

Summary of Contents for Cutler-Hammer DS6 Series

Page 1: ...specifications set forth by UL 508 IEC 60947 4 2 CE C Tick and CSA This leaflet covers basic installation and setup No publication can take into account every possible situation If you require furthe...

Page 2: ...Y DEATH OR SUBSTANTIAL PROPERTY DAMAGE DO NOT APPLY A DISCONNECT DEVICE ON THE OUTPUT OF THE DS6 SOFT START CONTROLLER UNLESS A MEANS TO TURN OFF THE DEVICE WHEN DISCONNECT SWITCH IS OPEN IS UTILIZED...

Page 3: ...llowable Fuse Size 200V 230V 460V hp hp hp DS6 34DSX041N0 N 40 10 10 30 HFD3150L 150A Class RK5 DS6 34DSX055N0 N 52 15 20 40 HFD3200L 200A Class RK5 DS6 34DSX068N0 N 65 20 25 50 HJD3250 200A Class RK5...

Page 4: ...3 24 Ready status contacts NO 0V 24 TOR Ready A2 EN A1 13 14 24 24V 0V 23 0V 24 A2 EN A1 13 14 24 23 Q1 Control Wiring Terminal Block Figure 5 Direct Start With Soft Stop Table 7 DS6 Terminal Control...

Page 5: ...soft start controller issues a START command by applying 24 Vdc to terminals EN and A1 Contacts 13 and 14 will close when the end of the ramp time is reached ote N Bypass contactors close at the end...

Page 6: ...tarting torque Mixer dry materials 15s 56 75 Pelletizing machine 20s 64 100 Pump piston 25s 30s 82 175 Possible high starting torque Pump centrifugal 10s 30s 37 25 Moving pavement unloaded 20s 37 25 E...