background image

Catalog Number Description

EGF1NODCNE100

N.O. 0.15 A @ 30 VDC, Normally Energized, 100 mA Range 

EGF1NODCDE100

N.O. 0.15 A @ 30 VDC, Normally De-Energized, 100 mA Range 

EGF1NCDCNE100

N.C. 0.15 A @ 30 VDC, Normally Energized, 100 mA Range 

EGF1NCDCDE100

N.C. 0.15 A @ 30 VDC, Normally De-Energized, 100 mA Range 

EGF3NOACNET3

N.O. 1 A @ 240 VAC, Normally Energized, 5/10/30 mA Range

EGF3NOACDET3

N.O. 1 A @ 240 VAC, Normally De-Energized, 5/10/30 mA 

Range

EGF3NODCNET3

N.O. 0.15 A @ 30 VDC, Normally Energized, 5/10/30 mA 

Range

EGF3NODCDET3

N.O. 0.15 A @ 30 VDC, Normally De-Energized, 5/10/30 mA 

Range

EGF3NCACNET3

N.C. 1 A @ 240 VAC, Normally Energized, 5/10/30 mA Range

EGF3NCACDET3

N.C. 1 A @ 240 VAC, Normally De-Energized, 5/10/30 mA 

Range

EGF3NCDCNET3

N.C. 0.15 A @ 30 VDC, Normally Energized, 5/10/30 mA 

Range

EGF3NCDCDET3

N.C. 0.15 A @ 30 VDC, Normally De-Energized, 5/10/30 mA 

Range

Introduction

The CurrentWatch™ EGF Series is a family of ground fault (earth 

leakage) sensors. Ground fault sensors help protect people, prod-

ucts, and processes from damage by ground fault conditions by 

monitoring all current-carrying conductors in grounded single- and 

three-phase delta or wye systems. They provide a contact output 

that can operate relays, contactors or signal automation systems.

Note:

N

This manual only covers solid state versions of the EGF Series (listed 

in the table above). For installation manuals covering other models in the EGF 

Series family, please contact Eaton Sensor Application Engineers.

Quick Install Guide

The below steps can be followed to quickly install a CurrentWatch 

EGF Series switch.

1.  Run all current carrying conductors through sensor window, 

using an auxiliary current transformer if conductors do not fit.

2.  Mount the sensor to a surface if needed.
3.  Connect output and power wiring:

a.  Use up to 14 AWG copper wires,
b.  Ensure power and load matches those shown on the sensor 

label. 

4.  Test the unit

a.  Pressing the “TEST” button will test the sensor’s internal 

circuits  

(

CAUTIONe: 

The output and any connected loads will 

switch during the test process)

Installation and Wiring

Considerations for installing and wiring EGF Series sensors…

• 

Run wire to be monitored through the aperture (opening) in the 

switch body, making sure all wires are oriented so that current 

flows in the same direction (see “Principal of Operation” section  

below).

• 

These sensors can be located in the same environment as 

motors, contactors, heaters, pull-boxes, and other electrical enclo-

sures.

• 

Mounting can be done in any position or hung directly on a wire 

with a wire tie.

• 

Be sure to leave at least one in.(25.4 mm) distance between sen-

sor and other magnetic devices. 

• 

Connect power and output wiring to the sensor, using up to 14 

AWG copper wire and tightening terminals to 7 in.-lbs / 0.79 N·m 

maximum torque.

• 

Make sure the power supply matches the power rating on the 

sensor label.

• 

Make sure the output load is less than or equal to the output rat-

ing on the sensor label.

Power

Output

G

X

Control Power

(Match Sensor Rating--See Label)

TEST

(+)
(-)

Power Supply LED

Contact Status LED

Load

Contactor, Relay, Shunt Trip Breaker...

(Do Not Exceed Rating--See Label)

Setpoint Adjust
Factory Calibrated and Covered
(Remove Cover, Adjust and 
Relabel if Required)

Output Power
(Match Sensor Rating--See Label)
For DC Output Versions...
Observe Polarity

Principal of Operation

Under normal conditions, the current in one wire of a two wire load 

is equal in strength but opposite in sign to the current in other wire. 

The two wires create magnetic fields that cancel, a condition known 

as “Zero Sum Current.” If any current leaks to ground (Ground Fault), 

the two currents become unbalances and there is a net resulting 

magnetic field. The EGF Series sensor detects this minute field and 

change the output state. This concept extends to three phase sys-

tems such as 3-wire Delta and to 4-wire Wye.

OptraoiNn

To test operation, gently press the TEST button. This simulates a fault 

and tests the internal switching circuits. The following operation should 

be observed. 

CAUTIONe:

 

Any circuit connected to the sensor will be operated.

Power

Output

Power

Interupt

A

B

C

N

3    Wye Power

3    Load

Power

Output

Power

Interupt

HOT

NEUT

1   Power

1   Load

Power

Output

Power

Interupt

A
B

3    Power

1    Load

Power

Output

Power

Interupt

A

B

C

3    Delta Power

3    Load

Models Covered In This Publication 

(Cont.)

2

EATON 

www.eaton.com

CurrentWatch™ EGF Series Ground Fault Sensors

120 VAC Powered, N.O. or N.C.,

Solid State Relay Output

Instructions Publication 

P51925

Effective July 2017

Summary of Contents for CurrentWatch EGF Series

Page 1: ...ок Опасно для жизни Только специалисты или проинструктированные лица могут выполнять следующие операции Levensgevaar door elektrische stroom Uitsluitend deskundigen in elektriciteit en elektrotechnisch geïnstrueerde personen is het toegestaan de navolgend beschreven werkzaamheden uit te voeren Livsfare på grund af elektrisk strøm Kun uddannede el installatører og personer der e instruerede i elekt...

Page 2: ... monitored through the aperture opening in the switch body making sure all wires are oriented so that current flows in the same direction see Principal of Operation section below These sensors can be located in the same environment as motors contactors heaters pull boxes and other electrical enclo sures Mounting can be done in any position or hung directly on a wire with a wire tie Be sure to leav...

Page 3: ...nt ground fault sensors are sensitive devices that require reasonable care in system design to avoid false trips caused by high electrical noise levels Keep in mind that the best way to reduce noise in a system is to suppress it at its source Keep the sensor power isolated from noisy circuits Do not power the sensor with the same circuit that switches contac tors or other high current inductive lo...

Page 4: ...ensors 2017 by Eaton All Rights Reserved Printed in USA Publication No P51925 004 July 2017 CurrentWatch EGF Series Ground Fault Sensors 120 VAC Powered N O or N C Solid State Relay Output Instructions Publication P51925 Effective July 2017 Eaton Industries GmbH Hein Moeller Straße 7 11 53115 Bonn Germany Eaton W126 N7250 Flint Drive Menomonee Falls WI 53051 USA Eaton Electrical Sector Sensors 1 8...

Reviews: