Wiring Diagrams

Connect control or monitoring wires to the sensor. Use up to 14 

AWG copper wire and tighten terminals to 7 in.-lbs / 0.79 N·m maxi-

mum torque. Be sure the output load does not exceed the switch 

rating. The DC output models are polarity sensitive.  

CAUTION! 

INCANDESCENT LAMPS CAN HAVE “COLD FILAMENT INRUSH” CURRENT 

OF UP TO TEN TIMES THEIR RATED AMPERAGE.  USE CAUTION WHEN 

SWITCHING LAMPS.

Output

Diagram

AC, Normally 

Open (N.O.) 

Models

DC, Normally 

Open (N.O.) 

Models

Ranges And Maximum Amps

Range 

Jumper

Range

Maximum 

Amps

Solid 

Core

Split Core

6 sec.

1 sec.

None

1-6 A

1.75-6 A

400 A

600 A

Mid

6-40 A

6-40 A

500 A

800 A

High

40-175 A

40-200 A

800 A

1,200 A

Troubleshooting

Problem

Solution

Switch is  

always  

tripped.

The jumper may be set in a range that is too low for current being 

monitored. Move jumper to the correct range.
The setpoint may be too low. Turn pot counter-clockwise to increase 

setpoint.
For DC models only, polarity might be mismatched. Check polarity on 

output wiring and correct as needed.
Switch may have been overloaded and contacts are burned out. Check 

the output load, remembering to include inrush on inductive loads 

(coils, motors, ballasts).

Switch will  

not trip.

The jumper may be set in a range that is too high for current being 

monitored. Move jumper to the correct range.
The setpoint may be too high. Turn pot counter-clockwise to decrease 

setpoint.
The monitored current may be below the minimum required. Loop the 

monitored wire several times through the aperture until the “sensed” 

current rises above the minimum. The sensed amps equals “actual 

amps” multiplied by the “number of loops.” Count loops on the inside 

of the aperture.
For split core models, the contact area may be dirty. Open the sensor 

and clean the contact area.

AC

Power

AC

Load

Monitored

Wire

Use caution when

switching lamps

(N.O. Model Shown)

DC

Power

DC

Load

Monitored

Wire

Use caution when

switching lamps

(N.O. Model Shown)

Hysteresis

Range 

Setting Hysteresis

Low

<

 

0.01 A

Mid

<

 

0.1 A

High

<

 

0.5 A

Specifications

AC Models

DC Models

Power Supply

Self Powered–No Power Supply Needed

Output

Isolated Solid State Switch

Output Rating

Standard Models: 1.0 A @ 

240 VAC 

Models Ending -04SC/-05SC:

   3.0 A @ 120 VAC

Models Ending -06SC/07SC:  

   15 A @ 120 VAC 

   10 A @ 240 VAC

Standard Models:

   0.15 A @ 30 VDC

ECSJ430SC:  

   0.15 A @ 30 VDC  

   Form C SPDT

Off-State Leakage

N.O. Models: < 10 µA 

N.C. Models: 2.5 mA

N.O. Models: < 10 µA 

N.C. Models: 1.4 mA

Response Time

0.47 - 2.5 seconds

Setpoint Range

Solid Core Models: 1-6, 6-40, 40-175 A 

Split Core Models: 1.75-6, 6-40 and 40-200 A

Hysteresis

Low: 6%; Mid: 4%; High: 3%

Overload

1-6 A: 6 sec. @ 400 A; 1 sec. @ 600 A 

6-40 A: 6 sec. @ 500 A; 1 sec. @ 800 A 

40-175 A: 6 sec. @ 800 A; 1 sec. @ 1,200 A

Isolation Voltage

UL Listed to 1,270 VAC, Tested to 5,000 VAC

Frequency Range

6-100 Hz

Sensing Aperture

Solid Core, Front Terminal Models: 0.55 in. (14 mm) dia. 

Solid Core, Top Terminal Models: 0.74 in. (19 mm) dia. 

Split Core Models: 0.85 in. (21.6 mm) sq.

Housing

UL94 V0 Flammability Rated

Environmental

Operating Temperature: -58 to +122°F (-50 to +50°C)

Approvals

UL Listed, E117028

UL Tested to Canadian Safety Standards

CE

RoHs Compliant

(ECSJ404SC and ECSJ405SC Not Listed)

3

EATON 

www.eaton.com

 

Instructions Publication 

P51919

Effective July 2017

CurrentWatch™ ECSJ Series Current Sensors 

Self-Powered AC Current Sensors with 

Jumper Selectable Current Ranges

Summary of Contents for CurrentWatch ECSJ Series

Page 1: ... possonoeseguire le operazioni di seguito riportate 触电危险 只允许专业人员和受过专业训练的人员进行下列工作 Электрический ток Опасно для жизни Только специалисты или проинструктированные лица могут выполнять следующие операции Levensgevaar door elektrische stroom Uitsluitend deskundigen in elektriciteit en elektrotechnisch geïnstrueerde personen is het toegestaan de navolgend beschreven werkzaamheden uit te voeren Livsfare ...

Page 2: ...a To set underload turn the pot about 1 8 turn further clock wise b To set overload turn the pot about 1 8 turn further counter clockwise For ECSJ421SC models the LED does not flash Steady LED on indicates contact has been opened ECSJ407SC ECSJ401SC and ECSJ421SC all provide a solid on LED to indicate the output has opened These models are all normally closed in the front terminal housing Introduc...

Page 3: ...nsed amps equals actual amps multiplied by the number of loops Count loops on the inside of the aperture For split core models the contact area may be dirty Open the sensor and clean the contact area AC Power AC Load Monitored Wire Use caution when switching lamps N O Model Shown DC Power DC Load Monitored Wire Use caution when switching lamps N O Model Shown Hysteresis Range Setting Hysteresis Lo...

Page 4: ...2017 by Eaton All Rights Reserved Printed in USA Publication No P51919 003 July 2017 CurrentWatch ECSJ Series Current Sensors Self Powered AC Current Sensors with Jumper Selectable Current Ranges Instructions Publication P51919 Effective July 2017 Eaton Industries GmbH Hein Moeller Straße 7 11 53115 Bonn Germany Eaton W126 N7250 Flint Drive Menomonee Falls WI 53051 USA Eaton Electrical Sector Sens...