Wiring Diagrams

Connect control or monitoring wires to the sensor. Use 12-22 AWG 

copper wire and tighten terminals to 4.5 in.-lbs / 0.51 N·m maximum 

torque.  Be sure the output load does not exceed the switch rating.

CAUTION! 

INCANDESCENT LAMPS CAN HAVE “COLD FILAMENT INRUSH” CURRENT OF 

UP TO TEN TIMES THEIR RATED AMPERAGE.  USE CAUTION WHEN SWITCHING 

LAMP LOADS CONNECTED TO THE SOLID-STATE OUTPUT.

CAUTION! 

DO NOT DISCONNECT OUTPUT TERMINALS UNDER LOAD.

Output

Diagram

Solid-State Output (N.O.)

Models

Mechanical Relay

(Form C) Models

Setpoint

Power Supply

12V AC/DC or 24V AC/DC

Solid-State

Output

1

2

Setpoint

Power Supply

12V AC/DC or 24V AC/DC

Mechanical

Relay Output

1

2

Ranges and Maximum Amps

Range

Jumper

Range

Maximum Amps

Solid Core

5 sec.

Continuous

Low

2-20 A

At least 1,000% of

range

At least 200% of range 

indefinitely

Mid

10-50 A

High

15-100 A

Troubleshooting

Problem

Solution

Switch is 

always 

tripped.

The jumper may be set in a range that is too low for current being moni-

tored.  Move jumper to the correct range.
The setpoint may be too low.  Turn pot clockwise to increase setpoint.
Switch may have been overloaded and contacts are burned out.  Check 

the output load, remembering to include inrush on inductive loads (coils, 

motors, ballasts).

Switch will 

not trip.

The jumper may be set in a range that is too high for current being 

monitored.  Move jumper to the correct range.
The setpoint may be too high.  Turn pot counter-clockwise to decrease 

setpoint.
Unit might not be powered.  Check power supply, power wiring, and 

green Power LED on switch.
Switch may have been overloaded and contacts are burned out.  Check 

the output load, remembering to include inrush on inductive loads (coils, 

motors, ballasts).

Specifications

Power Supply

12 VAC/DC (operates from 10-18 VAC/DC)

24 VAC/DC (operates from 20-28 VAC/DC)

Output Type and 

Rating

Isolated Solid-State Output,

0.15 A @ 240 VAC/DC

Mechanical Relay (Form C),

5 A General Purpose @ 240 VAC,

3 A Inductive @ 240 VAC,

3 A @ 30 VDC,

1/8 HP @ 240 VAC

Off-State Leakage None

Repeatability

0.5%

Setpoint Range

2-20, 10-40, 40-100 A

Hysteresis

5% of Setpoint

Isolation Voltage

3 kV

Frequency Range

DC to 400 Hz

Sensing Aperture

0.75 in. (19 mm)

Housing

UL94 V0 Flammability Rated

Environmental

Operating Temperature:

-40 to +60°C (-40 to +140°F)

Operating Temperature:

-20 to +50°C (-4 to +122°F)

Approvals

UL Listed, E117028

UL Tested to Canadian Safety Standards

CE

RoHs Compliant

3

EATON 

www.eaton.com

 

Instructions Publication 

P51991

Effective July 2017

CurrentWatch™ ECSD Series Current Switches

DC Current Switches with Jumper Selectable 

Current Ranges