RANGES AND MAXIMUM AMPS

Housing 
Style

Setpoint

Outputs

Maximum Input Amps

Continuous

6 sec.

1 sec.

Solid Core

Fixed (1.0A)

N.O.

250A

400A

1,000A

N.C.

150A

400A

1,000A

Adjustable (1-150A)

N.O.

150A

400A

1,000A

N.C.

150A

400A

1,000A

Split Core

Fixed (1.5A)

N.O.

250A

400A

1,000A

N.C.

150A

400A

1,000A

Adjustable 
(1.75-150A)

N.O.

150A

400A

1,000A

N.C.

150A

400A

1,000A

SETPOINT ADJUSTMENT

The CurrentWatch™ ECS Series setpoint is adjusted with a four-turn 
potentiometer (for models ending -SP) or a fi fteen-turn potentiometer 
(for models ending -SC). The pot is shipped factory set to the lowest 
setpoint, fully clockwise. Turning the pot counter-clockwise will increase 
the setpoint. The pot has a slip-clutch to prevent damage at either end 
of its rotation. To determine where the adjustment is, turn the pot all the 
way clockwise. This will return it to the minimum setpoint. 

Important Setpoint Adjustment Notes

•  Output contacts are solid-state. Check output status by applying 

voltage to the contacts and reading the voltage drop across the 
contacts. An Ohmmeter set on “continuity” will give misleading 
results.

•  It is recommended the setpoint be adjusted to allow for voltage 

variations of 10 to 15 percent.

•  Mounting can be done in any position or hung directly on wires 

with a wire tie

Typical Adjustment Steps

1.  Turn the pot to the minimum setpoint (four or fi fteen turns 

clockwise).

2.  Have normal operating current running through the switch. The 

output should be tripped since the pot is at its minimum setpoint. 
For units with an LED, it should be fl ashing fast (two to three times 
per second).

3.  Turn the pot counter-clockwise until the unit un-trips. This is 

indicated by the slow fl ashing of the LED (once every two to three 
seconds), or by changing of the output switch status.

4.  Now turn the pot clockwise slowly until the unit trips again. It is 

now set at the current level being monitored.

a.  To set underload, turn the pot about 1/8 turn further clockwise

b.  To set overload, turn the pot about 1/8 turn further counter-

clockwise

WIRING DIAGRAM

Connect control or monitoring wires to the sensor. Use up to 
14 AWG copper wire and tighten terminals to 5 inch-pounds torque. Be 
sure the output load does not exceed the switch rating.

CAUTION! Incandescent 
lamps can have “cold 
fi lament inrush” current 
of up to ten times their 
rated amperage. Use 
caution when switching 
lamps.

TROUBLESHOOTING

Problem

Solution

Switch is 
always tripped

The setpoint may be too low. Turn the pot counter-clockwise to 
increase the setpoint.

The switch may have been overloaded and the contacts are 
burned out. Check the output load, remembering to include inrush 
on inductive loads (coils, motors, ballasts).

Switch will 
not trip

The setpoint may be too high. Turn the pot clockwise to decrease 
the setpoint.

On split core models, the core contact area may be dirty. Open the 
switch and clean the contact area.

The monitored current may be below the minimum required. Loop 
the monitored wire several times through the aperture until the 
“sensed” current rises above the minimum. The sensed amps 
equals “actual amps” multiplied by the “number of loops.” Count 
loops on the inside of the aperture.

The switch may have been overloaded and the contacts are 
burned out. Check the output load, remembering to include inrush 
on inductive loads (coils, motors, ballasts).

SPECIFICATIONS

Solid Core

Split Core

Power Supply

Self Powered–No Power Supply Needed

Output

Magnetically Isolated Solid-State Switch

Output Rating

Normally Open Models: 0.15A, 240V AC/DC
Normally Closed Models: 0.20A, 135V AC/DC

Off-State Leakage

< 10 µA

Response Time

120 ms

Adjustable Setpoint Range

1-150A

1.75-150A

Setpoint Adjustment

15-Turn Potentiometer

4-Turn Potentiometer

Fixed Setpoints

1.0A

1.5A

Hysteresis

Approximately 5% of Setpoint

Overload

Fixed Setpoint, N.O. Models: 6 sec. @ 500A; 1 sec. @ 1,000A
All Other Models: 6 sec. @ 400A; 1 sec. @ 1,000A

Isolation Voltage

UL Listed to 1,270V AC, Tested to 5,000V AC

Frequency Range

6-100Hz

Sensing Aperture

0.74 in. (19mm)

0.85 in. (21.6mm)

Housing

UL94 V0 Flammability Rated

Environmental

Operating Temperature: -58 to +122° F (-50 to +50° C)
Humidity: 0-95% RH, Non-Condensing

Approvals

UL and ULC Listed
CE Certifi ed

392500221

AC or DC

Power

AC or DC

Load

Monitored Wire

Current Switch