12
INM F892 Rev 1
Part Numbers:
Carriers
Kits w/ F801
Kits w/ F802
F822-CA
F822-P*[-NR]
F822-2-P*[-NR]
F880-CA
F880-P*[-NR]
F880-2-P*[-NR]
F880-CL
F880-L*[-NR]
F880-2-L*[-NR]
F880-CR
F880-R*[-NR]
F880-2-R*[-NR]
F882-CA
F882-P*[-NR]
F882-2-P*[-NR]
F890-CA
F890-P*[-NR]
F890-2-P*[-NR]
F892-CA
F892-P*[-NR]
F892-2-P*[-NR]
WARNING:
EXPLOSION HAZARD - DO NOT DISCONNECT
EQUIPMENT UNLESS POWER HAS BEEN SWITCHED
OFF OR THE AREA IS KNOWN TO BE NON-HAZARDOUS.
HAZARDOUS (CLASSIFIED) LOCATION
Class I, Division 2, Groups A, B, C, D, T4
Class I, Zone 2, IIC T4
-40C <= Tamb <= 65C
-40C <= Tamb <= 50C (F802 total load > 60% of rated maximum)
To be installed in an IP54 or better enclosure
F8xx CARRIER
F801
or
F802
Plugged
into
Socket A
Power Supplied to the Carrier must be fused for 8A circuitry.
F801
or
F802
Plugged
into
Socket B
Diagnostic Module
Segment 1
Segment 2
Segment 3
Segment 4
Segment 5
Segment 6
Segment 7
Segment 8
+
-
s
+
-
s
+
-
s
+
-
s
+
-
s
+
-
s
+
-
s
+
-
s
+
-
s
+
-
s
+
-
s
+
-
s
+
-
s
+
-
s
+
-
s
Host 1
Host 2
Host 3
Host 4
Host 5
Host 6
Host 7
Host 8
Power A
Power B
Ground
Alarm Contact
Carrier May Contain a Single F801 or F802 module where redundancy is not needed ("-NR" option).
In such cases, only one Power Supply connection is needed. Also for the Alarm Contact
to work, an F800-BLK module must be installed in place of the missing F801 or F802 module.
24VDC Power Supplies
may be installed in the
Non-hazardous area.
Vmax = 24VDC (F801), 30VDC (F802)
24VDC
Power
Supply A
24VDC
Power
Supply A
This is a Chassis Ground
for EMC Compliance and
electrical safety.
This drawing is representative of the F8xx series of Carriers. There will be minor differences in the various models.
Kits contain 1 or 2 F801 or F802 modules along with the Carrier and Pluggable Connectors.
* =
S
for Pluggable Screw Terminal Connectors,
C
for Pluggable Cage Clamp Connectors.
Each of the 8 Segments (Hostx, Segmentx) are isolated from one another and from the Power Supplies.
Host Terminals connect to the Host Control system which may be in a non-hazardous area.
+
-
s
+
-
s
Diag Seg connectors
(not available on all carrier models)
Imax(-NR) = 420mA (F801), 580mA (F802)
Imax = 840mA (F801), 1.16A (F802)
Do not mix an F801 and F802 on the same Carrier.
Installation must be in accordance with the National Electrical Code (NFPA 70, Article 504),
ANSI/ISA-RP12.6, or the Canadian Electrical Code (CSA C22.1), as applicable.
Mike Strauser
Mike Strauser
CONTROL DRAWING FOR F8xx Carriers
CONTROL DRAWING FOR F8xx Carriers
CLASS I, DIV 2 (ZONE 2)
CLASS I, DIV 2 (ZONE 2)
HAZARDOUS LOCATIONS
HAZARDOUS LOCATIONS
2221 Yew Street, Forest Grove, Oregon 97116 USA
Date: 2/10/10
Date: 2/10/10
Title:
Approved By:
Drawing Number: 502-087
Drawing Number: 502-087
Rev.: D.0
Rev.: D.0
+
-
s
A1
A2
G
G
+
-
+
-
+
-
-
+