![background image](http://html.mh-extra.com/html/eaton/cooper-power-series/cooper-power-series_installation-instruction-and-service-manual_524278021.webp)
Figure 13. TB1 Eaton's connections.
(G) (R) (R) (L) (L) (OC) (DHR) (NL) (NL) (NL2) (HS) (HS) (#2) (G) (G) (#1) (V2) (V5) (V1) (V4) (C2) (C3) (20) (21) (23)
(G)
(V6) (V1)
(C)
White - Ground
Blue - R
aise
Green/Blac
k - L
ower
Orange/Blac
k - Drag Hand
R
ed/Blac
k - Neutral Light
Orange - Holding S
witc
h
White/Blac
k - S
ource PT
Blac
k - L
oad PT
Green - CT P
ositi
ve
R
ed - CT Neg
ati
ve
Table 4. CRA Kit Connections for Eaton/McGraw
Edison Voltage Regulators
Connection Point
Wire Color
V1
Black
G
White
C (bottom)
Red
C (top)
Green
HS
Orange
R1
Blue
V6
White/Black
NL
Red/Black
L1
Green/Black
DHR
Orange/Black
Motor Cap 1
Lt Blue/Black
Motor Cap 2
Black/White
17
CL-7 control replacement assembly installation instructions and service information
MN225017EN October 2016