withstand test results
The high-potential withstand tests provide information on
the dielectric condition of the recloser and the vacuum
integrity of the interrupters.
If the recloser passes the closed-contacts tests (Tests 1
and 2), but fails the open-contacts test (Test 3), the cause is
likely to be in the interrupter assembly. Retest each phase
individually to determine the failed phase or phases.
If the recloser does not pass Tests 1, 2, or 3, contact an
authorized service center or your Eaton representative.