type vsa12, vsa12b, vsa16, vsa20, and vsa20a operation and installation instructions

  MN280063EN   May 2017

Operation

 warNiNg

this equipment is not intended to protect human 

life. follow all locally approved procedures and safety 

practices when installing or operating this equipment. 

failure to comply can result in death, severe personal 

injury, and equipment damage. 

g102.1

 warNiNg

hazardous voltage. always use a hotstick when working 

with this equipment. failure to do so could result in 

contact with high voltage, which will cause death or 

severe personal injury. 

g108.1

 warNiNg

hazardous voltage. do not rely on the open position 

of the yellow operating handle or the contact position 

indicator; it does not ensure that the line has been 

de-energized. always establish a visible disconnect. 

failure to follow proper safety practices can result in 

contact with high voltage, which will cause death or 

severe personal injury. 

g114.1

VSA three-phase reclosers feature vacuum interruption and 

air insulation. Current interruption takes place in the vacuum 

interrupter assemblies that are suspended from the recloser 

cover by insulating supports. See Figures 12 and 13. The 

moving contacts, which are located in each interrupter 

assembly and driven by the recloser operating mechanism, 

close or open the circuit. Arc interruption takes place within 

one cycle while utilizing a stroke of approximately one-half 

inch.

figure 12. type vSa20 vacuum recloser with inspection 

cover removed.

figure 13. vSa20 vacuum interrupter assembly.

Recloser tripping and closing are initiated by signals from 

the recloser control unit. When current in excess of the 

programmed minimum trip level is detected on any phase 

or phases, the recloser control initiates a trip signal which 

energizes a solenoid in the operating mechanism of the 

recloser. When actuated, this solenoid trips the opening 

springs which opens the interrupter contacts.
Closing springs provide the force required to close the 

vacuum interrupters as well as the force required to charge 

the opening springs. A 240 Vac motor charges the closing 

springs through a multi-stage gear drive. When 240 Vac is 

present, the motor is automatically operated to keep the 

closing springs in a charged state.
To close the recloser, the control initiates a signal which 

energizes a solenoid in the recloser operating mechanism. 

Once actuated, the solenoid releases the closing springs, 

closing the vacuum interrupters. At the same time, the 

opening springs are charged and, when 240 Vac is present, 

the closing springs are charged. An external 240 Vac source 

is required to operate the drive motor.
Recloser tripping employs stored spring energy. The 240 

Vdc supply is not required to trip the recloser. When the trip 

solenoid is actuated by the 24 Vdc trip signal, the stored 

spring energy is released to open the recloser. The 24 Vdc 

trip signal is originated at the recloser control.

!

Bushing Lead

Vacuum Interupter

Bushing

Bushing Lead

Current Exchange Assembly

Support Stringer

Vacuum Interrupter

Summary of Contents for COOPER POWER SERIES

Page 1: ...Type VSA12 VSA12B VSA16 VSA20 and VSA20A operation and installation instructions COOPER POWER SERIES Reclosers MN280063EN Effective May 2017 Supersedes October 2002 S280 45 1...

Page 2: ...FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTE...

Page 3: ...gs and electrical mechanical Specifications 2 Dimensions and weights Dimensions and weights 3 Installation Installation procedure 4 Heaters 5 240 vac power connections 6 Remove recloser from service 6...

Page 4: ...hen working around high voltage lines and equipment and support our Safety For Life mission Safety information DANGER Hazardous voltage Contact with hazardous voltage will cause death or severe person...

Page 5: ...carrier for shipment Upon receipt inspect the carton for signs of damage Unpack the control and inspect it thoroughly for damage incurred during shipment If damage is discovered file a claim with the...

Page 6: ...Circuit Interrupting Rating Maximum X R Ration Number of Unit Operations 15 20 45 55 90 100 4 8 16 88 112 32 Total 232 Table 5 Electrical Specifications Description Trip Solenoid Operating voltage Vdc...

Page 7: ...298 11 75 K 1080 42 5 1257 49 5 L 413 16 25 514 20 25 M 159 6 25 260 10 25 N 108 4 25 210 8 25 All dimensions are mm inches Dimensions shown are approximate Figure 1 Outline dimensions and weights Mo...

Page 8: ...Perform high potential withstand tests Prior to installing the VSA recloser with the recloser in the OPEN position perform high potential withstand tests across each open interrupter assembly Refer to...

Page 9: ...VSA20A bushings are equipped with 1 1 4 12 UNF 2A threaded studs Figure 3 Typical recloser connections with switches to facilitate maintenance and with complete surge protection 7 Block ground sensing...

Page 10: ...utility procedures regarding removal of recloser from service AS Auxiliary Switch 152 Spring Position Switch 24 Vdc SP1 152 CC Close Coil Solenoid D Diodes 1N3209 152 SP2 Spring Position Switch 240 V...

Page 11: ...t Heaters Interrupter Enclosure 5K 3 5K Battery Charger accessory KA58VSM2 152 MCS 152 aa1 152 SP2 152 bb1 152 SP1 152 LS 152 CC 152 TC 152 a2 152 a1 2 1 3 4 6 8 7 5 Receptacle and Plug 1R X1K X2J X1...

Page 12: ...wired to a separate six point terminal block in the operator mechanism cabinet Figure 5 The available current ratios and terminal block terminations are shown in Table 8 Figure 6 Position of shorting...

Page 13: ...ontrol cable is wired to the accessory which transforms the control signal to trip and close the recloser Refer to Figures 8 and 9 Table 9 Cable Lengths for Substation Battery Power Interface Accessor...

Page 14: ...in Contacts are Open 152 H Manual Trip and Reset Switch when not in reset position will prevent a close 152 a Auxiliary Switch Contact Open when Main Contacts Open Figure 9 Substation Battery Power In...

Page 15: ...Mounting Electronic Control see detail Alternate Control Mounting for clarity operator on front of recloser is not shown Standard Control Cabinet Mounting Brackets FRONT KA55VS2 KA55VS4 double size co...

Page 16: ...75 C 406 16 483 19 D 292 11 5 318 12 5 All dimensions are mm inches Dimensions shown are approximate Model kg lbs VSA 12 12B 16 20 272 600 VSA20A 381 840 Figure 11 Outline dimensions and weights with...

Page 17: ...igure 12 Type VSA20 vacuum recloser with inspection cover removed Figure 13 VSA20 vacuum interrupter assembly Recloser tripping and closing are initiated by signals from the recloser control unit When...

Page 18: ...ure 14 Manual closing Closing springs must be charged prior to manual closing operation see the Testing Operation section of this manual There are two ways to manually close the recloser Refer to Figu...

Page 19: ...additional information and specific maintenance requirements including periodic maintenance inspection procedures refer to the maintenance manual Testing operation This recloser is used with microproc...

Page 20: ...nside of the operator cabinet door through the hole in the right hand side of the operator cabinet sealed with a bolt nut seal and onto the drive shaft see Figure 15 v Crank the motor in a countercloc...

Page 21: ...ential withstand tests at 37 5 kV rms 60 Hz or at 50 kV for 60 seconds See Figure 16 for test connection diagrams Test 1 1 Close the recloser contacts 2 Ground the recloser 3 Connect terminals 2 4 and...

Page 22: ...ative Replacement parts Replacement parts for Eaton reclosers are available through the factory Service Department To order replacement parts refer to the maintenance manual and S260 01 through S280 0...

Page 23: ...19 type vsa12 vsa12b vsa16 vsa20 and vsa20a operation and installation instructions MN280063EN May 2017 This page is intentionally blank...

Page 24: ...States Eaton com cooperpowerseries 2017 Eaton All Rights Reserved Printed in USA Publication No MN280063EN KA2048 0046 Rev 02 Eaton is a registered trademark All trademarks are property of their resp...

Reviews: