Instruction Leaflet 

IL29C109J

Effective  November 2013

Installation Instructions for ND, HND, NDC, CND,

CHND, CNDC Circuit Breakers with Digitrip OPTIM

 

Trip Unit and Powernet, and/or Zone Interlock

EATON CORPORATION

 www.eaton.com

NOTICE

Since the Digitrip OPTIM RMS trip units derive their 

operating power from the phase currents, and not

from the neutral current, passing current through 

the neutral sensor only will not properly test the

ground fault feature. 

Using a low-voltage (0-24 volt), high current, ac source,

apply a test current of 125% of the Digitrip OPTIM RMS 

Ground Fault Trip Unit pick-up setting through one

phase of the circuit breaker, as shown in Figure 4-2. 

This should cause the breaker to trip in less than 1 sec-

ond, and if an alarm indicator is supplied, it should oper-

ate. Reset the breaker and the alarm indicator. Repeat 

the test on the other

two phases.

If the system is a 4-wire system with a neutral current 

sensor, apply the same current as described above 

through one phase of the breaker, returning through the

neutral sensor, as shown in Figure 4-3. The breaker 

should not trip, and the alarm indicator, if supplied, 

should not operate. Repeat the test on the other two

phases.

Source

L

Low

Load 

Current Limiting 

Resistor

(if required) 

Figure 4-3 Connections for Ground Fault No-Trip Test 

with a Four- Wire System 

If the system is a 3-wire system with no neutral current 

sensor, apply the same current as described above 

through any two phases of the breaker, with the con-

nections exactly as shown in Figure 4-4. The breaker 

should not trip, and the alarm indicator, if supplied, 

should not operate. Repeat the test using the other two

combinations of breaker phases. 

CAUTION

FIELD TESTING SHOULD BE USED FOR FUNC-

TIONAL TESTING AND NOT FIELD CALIBRATION 

OF THE

OPTIM RMS GROUND FAULT 

TRIP UNIT. 

ANY TEMPORARY CONNECTION MADE FOR THE

PURPOSE OF CONDUCTING TESTS SHOULD BE 

RESTORED TO PROPER OPERATING CONDITIONS 

BEFORE RETURNING THE BREAKER TO SERVICE. 

The results of the test are to be recorded on the test

form provided with the equipment. 

Figure 4-4 Connectionsfor Ground Fault No-Trip Test

with a Three-Wire System 

L o w

V o l t a g e

S o u r c e

S o u r c e

L

C

R

C u r r e n t   L i m i t i n g

R e s i s t o r

( i f   r e q u i r e d )

Summary of Contents for CHND Series

Page 1: ...t IL29C109J Installation Instructions for ND HND NDC CND CHND CNDC Circuit Breakers with Digitrip OPTIM Trip Unit and Powernet and or Zone Interlock Contents Description Page 1 0 Introduction 2 2 0 In...

Page 2: ...for AC applications only and can be reverse fed They are listed in accordance with Underwriters Laboratories Inc Standard UL 489 and satisfy the requirements of International Electrotechnical Commiss...

Page 3: ...ment configuration the cir cuit breaker can be mounted using different styles of hardware The following steps describe how to mount the circuit breaker using standard hardware When special hardware is...

Page 4: ...t Breakers with Digitrip OPTIM Trip Unit and Powernet and or Zone Interlock EATON CORPORATION www eaton com Figure 2 2 Conductor Extensionsand Terminal Installation for 100 Rating 0 31 8 0 31 8 25 Tap...

Page 5: ...le and the PUSH TO TRIP but ton in the trip unit The circuit breaker handle has three positions two of which are shown on the cover with raised letteringto indicate ON and OFF On the handle ON OFF and...

Page 6: ...Bell Alarm Auxiliary Switch is only available on the OPTIM 1050 units If damaged a terminal block cover can be purchased through Eaton The part number is 4214844699 NOTICE 1 It is crucial to connect t...

Page 7: ...roblem Red On White Trip Color Green Off I On Figure 3 1 CircuitBreaker Switch circuit breaker to ON and OFF several times to be sure that the mechanism linkages operate freely and do not bind If mech...

Page 8: ...es that certain minimum instructions GROUND FAULT TEST RECORD FORM round Fault Test Records should be Retained by Those in Charge of the Building s lectrical Installation in order to be available to t...

Page 9: ...rough the neutral sensor as shown in Figure 4 3 The breaker should not trip and the alarm indicator if supplied should not operate Repeat the test on the other two phases Source L Low Load Current Lim...