background image

7

Instruction Leaflet 

IL29C109J

Effective  November 2013

Installation Instructions for ND, HND, NDC, CND,

CHND, CNDC Circuit Breakers with Digitrip OPTIM

Trip Unit and Powernet, and/or Zone Interlock

EATON CORPORATION

 www.eaton.com

Polarity

75 Trapped Holes 

Markings

Figure

2-7

Neutral Sensor Outline

cally. The inspection should include the following checks 

4-1 through 4-7.

WARNING

THE VOLTAGES IN ENERGIZED EQUIPMENT CAN 

CAUSE SEVERE PERSONAL INJURY OR DEATH. 

BEFORE INSPECTING THE CIRCUIT BREAKER IN

AN ELECTRICAL SYSTEM, MAKE SURE THE CIR-

CUIT BREAKER IS SWITCHED TO THE OFF POSI-

TION AND THAT THERE IS NO VOLTAGE PRESENT 

WHERE WORK IS TO BE PERFORMED. SPECIAL 

ATTENTION SHOULD BE PAID TO REVERSE FEED 

SENT.

APPLICATIONS TO ENSURE NO VOLTAGE IS PRE-

CAUTION

SOME COMMERCIAL CLEANING AGENTS WILL 

DAMAGE THE NAMEPLATES OR MOLDED PARTS. 

VENTS USED TO CLEAN THE CIRCUIT BREAKER 

ARE SUITABLE FOR THE JOB. 

MAKE SURE THAT CLEANING AGENTS OR SOL-

Remove dust, dirt, soot, grease, or moisture from 

the surface of the circuit breaker using a lint-free dry 

cloth, brush, or vacuum cleaner. 

Do not blow debris into 

circuit breaker.  If contamination is found, look for the

source and eliminate the problem.

Red - On

White - Trip 

Color 

Green - Off

\

I

On

Figure 3-1 Circuit Breaker

Switch circuit breaker to ON and OFF several times 

to be sure that the mechanism linkages operate freely 

and do not bind. If mechanical linkages do not operate 

freely, replace circuit breaker. 

With the circuit breaker in the ON position, press 

the PUSH-TO-TRIP button to mechanically trip the cir-

cuit breaker.  Trip, reset, and switch circuit breaker ON

several times. If mechanism does not reset each time 

the circuit breaker is tripped, replace the circuit breaker. 

Check base, cover, operating handle, and handle

barrier for cracks, chipping, and discoloration. Circuit 

breaker should be replaced if cracks or severe discol-

oration is found. 

Check wire connecting terminals and other type bus

bar connectors for looseness or signs of overheating.

Overheating will show as discoloration, melting, or 

blistering of conductor insulation, or as pitting or melting 

of conductor surfaces due to arcing. If there is no evi-

dence of overheating or looseness, do not disturb or 

tighten the connections. If there is evidence of overheat-

ing, terminations should be cleaned or replaced. Before 

re-energizing the circuit breaker, all terminations and 

cable should be refurbished to the originally installed 

condition.

Check circuit breaker mounting hardware, and tight-

en if necessary. 

Exposure to certain types of chemicals can cause 

Summary of Contents for CHND Series

Page 1: ...t IL29C109J Installation Instructions for ND HND NDC CND CHND CNDC Circuit Breakers with Digitrip OPTIM Trip Unit and Powernet and or Zone Interlock Contents Description Page 1 0 Introduction 2 2 0 In...

Page 2: ...for AC applications only and can be reverse fed They are listed in accordance with Underwriters Laboratories Inc Standard UL 489 and satisfy the requirements of International Electrotechnical Commiss...

Page 3: ...ment configuration the cir cuit breaker can be mounted using different styles of hardware The following steps describe how to mount the circuit breaker using standard hardware When special hardware is...

Page 4: ...t Breakers with Digitrip OPTIM Trip Unit and Powernet and or Zone Interlock EATON CORPORATION www eaton com Figure 2 2 Conductor Extensionsand Terminal Installation for 100 Rating 0 31 8 0 31 8 25 Tap...

Page 5: ...le and the PUSH TO TRIP but ton in the trip unit The circuit breaker handle has three positions two of which are shown on the cover with raised letteringto indicate ON and OFF On the handle ON OFF and...

Page 6: ...Bell Alarm Auxiliary Switch is only available on the OPTIM 1050 units If damaged a terminal block cover can be purchased through Eaton The part number is 4214844699 NOTICE 1 It is crucial to connect t...

Page 7: ...roblem Red On White Trip Color Green Off I On Figure 3 1 CircuitBreaker Switch circuit breaker to ON and OFF several times to be sure that the mechanism linkages operate freely and do not bind If mech...

Page 8: ...es that certain minimum instructions GROUND FAULT TEST RECORD FORM round Fault Test Records should be Retained by Those in Charge of the Building s lectrical Installation in order to be available to t...

Page 9: ...rough the neutral sensor as shown in Figure 4 3 The breaker should not trip and the alarm indicator if supplied should not operate Repeat the test on the other two phases Source L Low Load Current Lim...

Page 10: ...eaflet IL29C109J Effective November 2013 Installation Instructions for ND HND NDC CND CHND CNDC Circuit Breakers with Digitrip OPTIM Trip Unit and Powernet and or Zone Interlock EATON CORPORATION www...

Page 11: ...eaflet IL29C109J Effective November 2013 Installation Instructions for ND HND NDC CND CHND CNDC Circuit Breakers with Digitrip OPTIM Trip Unit and Powernet and or Zone Interlock EATON CORPORATION www...

Page 12: ...further information is required you should consult an authorized Eaton sales representa tive The sale of the product shown in this literature is subject to the terms and conditions outlined in appropr...

Reviews: