Instruction Booklet 

IB 70-8704

Effective January 2009

Eaton Corporation’s Family of Manual Transfer Switches
for Residential and Light Commercial Applications

eaton corporation

 www.eaton.com

Figure 3. Connection Locations for a Separately Derived System.

Connection for a Non-Separately Derived System:

2.  For portable generators that are configured as a  

Non- Separately Derived

 system.    

a.  Connect the two hot wires from the utility to the utility 

breaker poles #1 and #2.  Connect the utility neutral to the 

utility neutral lug.  See Figure 3 for clarification.

b.  Connect the two hot wires from the generator to the gen-

erator breaker poles #1 and #2.  Connect the generator 

neutral to the neutral bar.  See Figure 3 for clarification.

 

dANger

FOr A NON-sepArATely derIved sysTem dO NOT CONNeCT The  

UTIlITy Or geNerATOr NeUTrAls TO The UTIlITy breAker Or 

geNerATOr breAker NeUTrAl pOle.  These NeUTrAls mUsT be TIed 

TOgeTher AT The NeUTrAl bAr.  FAIlUre TO dO sO wIll leAd TO 

eqUIpmeNT FAIlUre, FIre, Or pOssIble deATh dUe TO A FlOATINg 

NeUTrAl CONdITION.  

Do 

Not

 Connect 

the Utility or 

Generator 

Neutrals to the 

Breaker if the 

Generator is 

Configured as a 

Non-Separately 

Derived

 System.

Leave These 

Poles Empty.

Utility Pole #1

Utility Neutral

Utility Pole #2

Generator Neutral

Generator Pole #1

Generator Pole #2