Instruction Booklet 

IB 70-8704

Effective January 2009

Eaton Corporation’s Family of Manual Transfer Switches

for Residential and Light Commercial Applications

eaton corporation

 www.eaton.com

Figure 1. Manual Transfer Switch with Door Open.

These Manual Transfer Switches utilize 3-pole switching devices to 

determine which power source, utility or generator, are powering 

the nine emergency circuits.  The 3-pole switching devices are inter-

locked via a manual slide type interlock.  The intent of the interlock is 

to ensure that only ONE source is powering the emergency circuits 

and to prevent back feeding of the utility with the generator or inad-

vertent paralleling of the utility and generator sources.  

Figure 2. Connection Locations for a Separately Derived System.

Connection for a Separately Derived System:

1.  For generators that are configured as a 

Separately Derived

 

system.  These units typically contain GFCI protection on the 

generator.  

a.  Connect the two hot wires from the utility to the utility 

breaker poles #1 and #2.  Connect the utility neutral to the 

utility breaker pole #3.  See Figure 2 for clarification.

b.  Connect the two hot wires from the generator to the  

generator breaker poles #1 and #2.  Connect the generator 

neutral to the generator breaker pole #3.  See Figure 2 for 

clarification.

 

CAUTION

FOr A sepArATely derIved sysTem FAIlUre TO CONNeCT As 

desCrIbed IN These INsTrUCTIONs wIll resUlT IN NUIsANCe TrIp-

pINg OF The geNerATOr gFCI CIrCUIT breAker.

Slide Interlock   

(To operate, turn 

the utility breaker 

to the OFF  

position.  Lift the 

interlock and hold.  

Turn the generator 

breaker to the ON 

position.  Release 

the interlock.

Reverse these 

steps to power 

loads via utility). 

Utility Breaker Shown 

in the ON Position

Generator Breaker 

Shown in the OFF 

Position

Utility Pole #2

Utility Pole #1

Utility Pole #3

Generator Pole #1
Generator Pole #2
Generator Pole #3