Effective January 2009
Supplement to IB 70-8447

CH10GEN5030SN
CH10GEN5030RSN
CH10GEN5050SN
CH10GEN5050RSN

Instruction Booklet 

IB 70-8704

Eaton Corporation’s Family of Manual Transfer Switches

for Residential and Light Commercial Applications

instruction and operation 
Manual for eaton 
emergency Generator 
panel Model numbers:

• 

CH10GEN5030SN

• 

CH10GEN5030RSN

• 

CH10GEN5050SN

• 

CH10GEN5050RSN

Introduction

The Eaton 10 Circuit Manual Transfer Switch is 

intended to be used with Eaton generators but 

may be used with any generators.  These Manual 

Transfer Switches are rated for 50 amp utility input 

and 30 amp or 50 amp generator input respec-

tively at 240 Vac.  These devices come equipped 

to power nine emergency circuits.  There are eight 

single-pole emergency circuit breakers and one 

2- pole emergency circuit breaker included.
These devices are intended for use with genera-

tors that are wired as either Separately Derived 

systems (neutral and ground bonded together 

at the generator – typically protected by a GFCI, 

ground fault circuit interrupter, on the generator) 

or Non-Separately Derived systems (neutral and 

ground are NOT bonded at the generator).  Refer 

to the NFPA 70, National Electrical Code, for 

proper connection and further definition.
Contact the generator manufacturer if you 

are unsure how the generator is configured 

(Separately Derived or Non-Separately Derived).  It 

is extremely important that you know this informa-

tion prior to connecting the generator to this or 

any other transfer switch.