Section 1: System installation and design
Alarm counter (Option 7 .13 of EN54 pt 2)
The Panel has provision to record the number of instances that the CIE enters the
fire alarm condition .
The information is available at access level 2 .
TEST (Option 16 of EN54)
The Panels equipped with the test option and can be implemented by either
Zone or Address .
Alarm verification
The Panel has the facility for global alarm verification where the detector alarm
decision is integrated over 30 seconds .
Cable & wiring
Only the cable types listed below are allowable for loop connections .
1.
Enhanced Fire TUF™
2.
Fire TUF™
3.
FP200
4.
MICC
When choosing your preferred cable type, you must take note of the following cable
and wiring requirements .
1.
The cable must be 2 core screened with an over sheath .
2.
Maximum loop length with any of the above cables is 2KM .
3.
Maximum volt drop must be limited to 7 volts .
4.
The conductors should be 1 .5mm minimum .
5.
Multicore cable should not be used for detector wiring .
6.
Different loops should NEVER be run within the same cable .
7.
Loop feeds and returns should never be used within the same cable .
Cable resistance
Core diameter
Typical FP200 resistance
1.0mm²
18.1 Ohms/km/Core
1.5mm²
12.1 Ohms/km/Core
2.5mm²
7.41 Ohms/km/Core
4.0mm²
4.61 Ohms/km/Core