16
INSTALLATION AND OPERATION MANUAL
25-16327-B November 2020 www.eaton.com
Section 1: System installation and design
AUX 2
Max Load
: 60 mA
Fused (PTC3)
: 1 .1A polyswitch
Fault routing equipment
Max Load
: <10 mA
Fused (PTC1)
: 100mA polyswitch
End of Line resistor
: 2K
Auxiliary 24V supply
Nominal Voltage : 24 Volts ±10%
Fuse (PTC5)
: 100 mA Polyswitch
Maximum current
: 30 mA
This output is not to be used for Fire protecting equipment or Fire alarm routing
Equipment .
Any power taken from the alarm system will effect the standby duration .
Mechanical specification
Weight including batteries : 9 Kg
Weight excluding batteries
: 4 Kg
Dimensions (Standard batteries) : 395mm(L) x 270mm(H) x 115mm(D)
Type of Material (backbox) : Mild Steel (Power Coated)
Type of Material (Facia) : PC/ABS
Flammability Rating
: UL 94 V0
Total Number of knockouts
: 11
Diameter of Knock out
: 20mm
TERMINAL BLOCKS : DO NOT USE EXCESSIVE FORCE WHEN TIGHTENING THE
SCREWS ON THE TERMINAL BLOCK