121
Mounting- and Operating Instruction CEAG DualGuard-S
40071860347 January 2020 www.ceag.de
47 DualGuard-S US30
Technical description
Field
Dimensions (W x H x D):
2070x800x405 mm
Colour:
RAL 7035
Weight:
165 kg
Assembly:
Only set up on non-combustible ground (e.g. con-
crete).
Degree of protection:
IP21, optional IP31, on request IP54
Protection class:
I
Ambient temperature:
-5°C to +35°C
Degree of pollution:
2
Electromagnetic compatibility:
Industry EN 61000-6-2, Commercial EN 61000-6-3
Rated voltage (Mains):
UN = 400/230 V AC
F1
Rated current (Mains):
IN = 80 A
Rated voltage (Battery):
216 V DC
F3
Rated current (Battery):
IN =80 A
Rated Frequency:
50 or 60 Hz
Overvoltage category:
Mains: III / Battery: II
Max. connected load:
At +35°C < 17,3 KW
Maximum numbers of modules:
Controller ACU DG / HMI:
1
A1
PSU:
1-2
B1
SKU.1.1 CG-S:
B2-E
1x6A
0-30
2x3A
0-30
4x1,5A
0-20
Max. numbers luminaire circuits:
88
A2-4
Terminals:
ACU DG
2,5mm² Rigid/ 1,5mm² flexible
A1
Luminaire circuits
4 mm² Rigid/flexible
A2-4
Battery feed
35 mm² Rigid/flexible
F3
Battery through-wiring
35 mm² Rigid/flexible
F4
Mains feed
35 mm² Rigid/flexible
F1
Mains through-wiring
35 mm² Rigid/flexible
F2
Order number accesories:
Cupboard base 100mm
40071362282
Cupboard base 200mm
40071362283
Door hinge left
40071362301
Special locking profile half cylinder
40037079790
IP 31 Retrofit kit
40071362291