10
Eaton BladeUPS DoS Installation Instructions P-164000613—Rev 3
Figure 9. Lifting the BladeUPS Module into the Cabinet
7.
For the second BladeUPS module.
Repeat steps 3-6 for the second BladeUPS module.
8.
Remove the eight screws on the bottom battery cover plate. Repeat to remove the top battery cover plate.
Retain the plates and the screws (see Figure 11).
Figure 10.
Figure 11. Remove Top and Bottom Battery Covers
9.
On each BladeUPS back panel, verify that input circuit breakers (CB1 and CB2) on both BladeUPS back
panels are in the OFF position. The OFF position is down and a small OFF label is visible on the circuit
breaker switch (see Figure 12).
Note:
On both BladeUPS back panels, CB2 is above the Input-Output Wire and CB1 is below the
Input-Output Wire.
Figure 12. CB1 and CB2 in OFF Position