background image

EF009SB 

1

, EF009SBWP 

2

, EF009 

3

, EF009WP 

4

BiWire Ultra Range (Conventional compatible)

Effective October 2019

Installation Instructions

INSTALLATION INSTRUCTIONS

   25-12766-G  October 2019

15

DoP0010

DoP0011

DoP0012

DoP0013

Specification

Supply voltage (BiWire alarm)

25.5~35 Vdc

Supply voltage (BiWire standby) 18~25.5 Vdc
Supply voltage (conventional)

18~35 Vdc

Cable size/type

0.5~2.5mm

2

/FIRETUF, FP200 or MICC

Standby current (BiWire mode)

<15μA

Current (high volume) Sdr only =

4.7mA, AV = 11mAx

Current (low volume) Sdr only =

2.6mA, AV = 8.7mA

Sound output (high volume)*

89 +/- 3dB(A) : All tones

Sound output (low volume)*

99 +/- 3dB(A) : All tones

89 +/- 3dB(A) : All tones

Operating temperature

-25 to +70ºC (93% ± 3%RH)

Material

ABS FR plastic

Environmental category

Type A= IP21C/ Type B= IP66

Tones

3, See section 3

Flash rate

0.5Hz (N/A to EF009(WP))

Flash on period

60ms (N/A to EF009(WP))

The devices have no serviceable component so no maintenance 

is required. *For full tone and polar node SPL data please refer 

to M14-002.

EN54-3:2001+A1:2002+A2:2006

EN54-23:2010

0905

Wall sounder/beacon
Wall sounder

Wall sounder/beacon IP66
Wall sounder IP66

2. Connection details

1a. Mounting base (IP21C)

1b. Mounting base (IP66C)

 50 

 50 

 60 

(i) Drill required holes for

    cable gland fixing.

(iii) Fix to mounting surface

     using two suitable screws.

(ii) Drill out the required 

     fixing holes.

Drill position for rear 

cable entry

Drill position for 

glands

 50 (IP33) 

 50 (IP33) 

 75 (IP66) 

 97 (IP66) 

 62 (IP33) 

(i) Drill required holes for cable gland fixing (top or bottom) 

    and ensure glands are suitable for required IP rating.

(ii) Fix to mounting surface using four suitable screws.

Drill position 

for glands

Use these four holes 

to ensure IP66 integrity

1

2

3

4

5

1

On

Off

3. Switch position meaning

1, Sounder on/off (AV version only)

2, Volume high (Off)/low (On)

3, Tones

4, Tones

5, Mode: On = BiWire, Off = Conventional

Continuous: 3=On, 4=On (984Hz)

Bell: 3=On, 4=Off  (1440Hz)

Alternating: 3=Off, 4=On (644/984Hz)

{

OUT

IN

SCREEN

ZONE OUT

ZONE IN

+VE  -VE

+VE  -VE

ZONE OUT

ZONE IN

Screen must be continuous along entire length of line.

  Note

  All products meet minimum requirements of IP33C in 

  accordance with EN54-3.