EF009SB
1
, EF009SBWP
2
, EF009
3
, EF009WP
4
BiWire Ultra Range (Conventional compatible)
Effective October 2019
Installation Instructions
INSTALLATION INSTRUCTIONS
25-12766-G October 2019
15
DoP0010
DoP0011
DoP0012
DoP0013
Specification
Supply voltage (BiWire alarm)
25.5~35 Vdc
Supply voltage (BiWire standby) 18~25.5 Vdc
Supply voltage (conventional)
18~35 Vdc
Cable size/type
0.5~2.5mm
2
/FIRETUF, FP200 or MICC
Standby current (BiWire mode)
<15μA
Current (high volume) Sdr only =
4.7mA, AV = 11mAx
Current (low volume) Sdr only =
2.6mA, AV = 8.7mA
Sound output (high volume)*
89 +/- 3dB(A) : All tones
Sound output (low volume)*
99 +/- 3dB(A) : All tones
89 +/- 3dB(A) : All tones
Operating temperature
-25 to +70ºC (93% ± 3%RH)
Material
ABS FR plastic
Environmental category
Type A= IP21C/ Type B= IP66
Tones
3, See section 3
Flash rate
0.5Hz (N/A to EF009(WP))
Flash on period
60ms (N/A to EF009(WP))
The devices have no serviceable component so no maintenance
is required. *For full tone and polar node SPL data please refer
to M14-002.
EN54-3:2001+A1:2002+A2:2006
EN54-23:2010
0905
Wall sounder/beacon
Wall sounder
Wall sounder/beacon IP66
Wall sounder IP66
2. Connection details
1a. Mounting base (IP21C)
1b. Mounting base (IP66C)
50
50
60
(i) Drill required holes for
cable gland fixing.
(iii) Fix to mounting surface
using two suitable screws.
(ii) Drill out the required
fixing holes.
Drill position for rear
cable entry
Drill position for
glands
50 (IP33)
50 (IP33)
75 (IP66)
97 (IP66)
62 (IP33)
(i) Drill required holes for cable gland fixing (top or bottom)
and ensure glands are suitable for required IP rating.
(ii) Fix to mounting surface using four suitable screws.
Drill position
for glands
Use these four holes
to ensure IP66 integrity
1
2
3
4
5
1
On
Off
3. Switch position meaning
1, Sounder on/off (AV version only)
2, Volume high (Off)/low (On)
3, Tones
4, Tones
5, Mode: On = BiWire, Off = Conventional
Continuous: 3=On, 4=On (984Hz)
Bell: 3=On, 4=Off (1440Hz)
Alternating: 3=Off, 4=On (644/984Hz)
{
OUT
IN
SCREEN
ZONE OUT
ZONE IN
+VE -VE
+VE -VE
ZONE OUT
ZONE IN
Screen must be continuous along entire length of line.
Note
All products meet minimum requirements of IP33C in
accordance with EN54-3.