3.5 Panel Configuration
Silence Mode Disabled
With switch 3 of SW12 on the panel main board set to
Silence
Mode Disabled
the panel will re-sound all fire alarm devices
after the panel has been silenced with any new fire conditions
detected (Figure 29).
Silence Mode Enabled
With switch 3 of SW12 on the panel main board set to
Silence
Mode Enabled
the panel will NOT re-sound the fire alarm
devices after the panel has been silenced regardless of any
new fire conditions detected.
Zone Configuration
Set SW3 and SW5 as shown in Figure 30 and the
accompanying table.
Zone #
BiWire Mode
Standard Conventional
Intrinsically Safe Conventional
1
SW3.1 = N/A
SW3.1 = OFF
SW3.1 = ON
SW5.1 = ON
SW5.1 = OFF
SW5.1 = OFF
2
SW3.2 = N/A
SW3.2 = OFF
SW3.2 = ON
SW5.2 = ON
SW5.2 = OFF
SW5.2 = OFF
3
SW3.3 = N/A
SW3.3 = OFF
SW3.3 = ON
SW5.3 = ON
SW5.3 = OFF
SW5.3 = OFF
4
SW3.4 = N/A
SW3.4 = OFF
SW3.4 = ON
SW5.4 = ON
SW5.4 = OFF
SW5.4 = OFF
5
SW3.5 = N/A
SW3.5 = OFF
SW3.5 = ON
SW5.5 = ON
SW5.5 = OFF
SW5.5 = OFF
6
SW3.6 = N/A
SW3.6 = OFF
SW3.6 = ON
SW5.6 = ON
SW5.6 = OFF
SW5.6 = OFF
7
SW3.7 = N/A
SW3.7 = OFF
SW3.7 = ON
SW5.7 = ON
SW5.7 = OFF
SW5.7 = OFF
8
SW3.8 = N/A
SW3.8 = OFF
SW3.8 = ON
SW5.8 = ON
SW5.8 = OFF
SW5.8 = OFF
Figure 29 . silence mode setting
Figure 30 . Zone mode setting