For more information visit: www.chfire.com
IM05805022K
Instruction Booklet
Page
20
Effective: January 2012
ATC-300+ Automatic
Transfer Switch Controller
Plant Exercising in the Load Exercising Mode is “Failsafe”. If the
generator fails during testing for any reason, the ATC-300+ will
signal the transfer switch to return to the Source 1 power source.
The ATC-300+ will display “FAILSAFE” until a pushbutton is
pressed.
5.10 Program Mode
The ATC-300+ Controller is fully programmable from the device’s
faceplate once the Password has been correctly entered. Any
operator associated with programming the ATC-300+ Controller
will quickly discover that ATC-300+ programming is just a matter
of simple, repetitive steps. However, because of the importance
placed on this function and its critical relationship to the proper
functioning of the system, Section 6 of this manual is dedicated
to the Program Mode. Refer to that section and Table 2 for
details.
Section 6: Programming
6.1 Introduction
The ATC-300 Controller is fully programmable from the device’s
faceplate. Users can reprogram setpoints as well as other param-
eters. The time, date, and setpoints can only be changed while
the device is in the Program Mode.
Program Mode is achieved by entering a valid password when
prompted by the Setpoints screens. The Unit Status LED will blink
at a faster rate when viewing the setpoints while in Program
Mode.
WHILE IN THE PROGRAM MODE, THE ATC-300+ CONTROLLER IS
NEVER OFF-LINE AND CONTINUES TO FUNCTION IN ACCORDANCE
WITH PREVIOUSLY PROGRAMMED SETPOINTS.
6.2 Password
To enter the Program Mode, the ATC-300+ Controller requires a
password to prevent unauthorized persons from modifying set-
point values.
There are five screens related to the password, which is a four-
digit number from 0000 to 9999.
1.
VIEW
YES
SETPOINTS?
Use the Increase or Decrease pushbuttons to select Yes, then use
the Step/Enter pushbutton to enter the selection and move to the
next screen.
2.
CHANGE
YES
SETPOINTS?
Use the Increase or Decrease pushbuttons to select Yes or No,
then use the Step/Enter pushbutton to enter the selection and
move to the next screen. If No is selected, the user will be able
to review the setpoints but not make any changes. If Yes is
selected, the Password screen will appear.
3.
PASSWORD
0000
(Use Inc/Dec)
Use the Increase or Decrease keys to scroll to the desired value
(0 - 9) for the first digit, then use the Step/Enter key to enter the
value and move to the next digit. Repeat for remaining three dig-
its. After all four numerals of the password are entered, press the
Step/Enter pushbutton to enter the password and proceed to the
next screen. If an invalid password is entered, the LCD Display
shall read “Invalid Password” and the user must press the Step/
Enter pushbutton to initiate another password entry sequence.
Note:
The factory default password is “0300”. If the password is forgot-
ten, contact the factory for the backdoor password.
NOTICE