1.7 Main bus
The main bus enclosure is mounted on top of the 80-inch tall vertical
sections . Main bus enclosure may consist of a 1,000 A, 1,200 A,
2,000 A, or 3,000 A rated main bus and/or 1,000 A rated variable
frequency drive (VFD) bus . The standard bus is uninsulated and can
be silver or tin plated . Option of insulated bus is available . The main
bus enclosure in a starter section may include vertical bus drops to
connect to the starter(s) . The main bus enclosure in an incoming
line section may include vertical bus drops to connect the incoming
line cables .
Only bottom entry cables option is available .
Figure 6. Main bus assembly.
Main bus assembly
Main bus assembly
(Shown with VFD bus option)
VFD vertical
bus drops
Variable frequency drive bus
Main bus
Main bus vertical
bus drops
Support