Instruction Book    

IB182221EN   September 2017   www.eaton.com

GE AM [Cable or Hard Bus Application]

Ground and Test Device

SECTION 4:  DESCRIPTION AND OPERATION

The G&T is a draw out device that can be inserted into a circuit 

breaker compartment in the same manner as the GE AM Air Circuit 

Breaker and Vacuum Replacement Circuit Breaker. It can be ordered 

as a single terminal device or a double terminal Ground and Test 

Device. It may also be ordered as a cable or hard bus type. Each 

terminal is isolated from each other and the ground bus connections 

by insulating barriers. The upper and lower terminals are accessible 

upon opening the respective front hinged door. The ground 

connection is located in the lower section of the device.

 WARNING

IT IS CRITICAL THAT THE BUS OR LINE TERMINALS BE CORRECTLY 

IDENTIFIED FOR EACH CIRCUIT BREAKER COMPARTMENT BEFORE USING 

THIS DEVICE.

Type GE AM-13.8 manual Ground & Test devices are also available 

with either the upper or lower terminals only.

4.1  INSULATING BARRIERS

Insulating barriers are red pieces of GPO-3 glastic material used 

to isolate the primary terminals from each other and the ground 

connections. They are attached to the Ground and Test Device frame 

using insulated hardware. Using other hardware than those provided 

will affect the insulating integrity of the Ground and Test Device.

4.2  BUSHINGS AND DISCONNECTING CONTACT 

ASSEMBLIES

The line and load bushing assemblies, which are the primary circuit 

terminals of the Ground and Test Device, consist of six silver 

plated conductors. Solid Stab type primary disconnecting contacts 

at the ends of the conductors provide means for connecting and 

disconnecting the G&T device to the bus terminals in the swtichgear 

circuit breaker compartment.

4.3  INTERLOCKS

The only interlocks associated with these Ground and Test Devices 

are the Kirk

®

 Key interlocks located on the front of the device. 

(Figure Set 3.3) This protects the user from having both top and 

bottom hinged doors open at the same time. While either the top or 

bottom door is unlocked, the key is unable to be removed from the 

lock. To remove the key, close the appropriate door and turn the key. 

This will lock the door and the key will now be able to be removed 

and inserted into the other lock. This feature is not applicable for 

single terminal G&T devices.

 NOTICE

ONLY ONE KEY WILL BE PROVIDED WITH EACH GROUND AND TEST 

DEVICE. THIS PREVENTS THE INTERLOCKING MECHANISM FROM BEING 

BYPASSED. IF A KEY IS LOST, CONTACT EATON FOR A REPLACEMENT. 

THIS FEATURE IS NOT APPLICABLE FOR SINGLE TERMINAL GROUND AND 

TEST.

 DANGER

INTERLOCKS ARE PROTECTIVE DEVICES FOR PERSONNEL AND 

EQUIPMENT. DO NOT BYPASS, MODIFY, OR MAKE INOPERABLE ANY 

INTERLOCKS. DOING SO COULD CAUSE DEATH, SERIOUS PERSONNEL 

INJURY, AND / OR PROPERTY DAMAGE.

4.4  GROUNDING CONTACTS

The grounding contact is a solid bus, which grounds the device by 

engaging the switchgear circuit breaker compartment grounding 

bus when the G&T device is lifted into the “connect” position. The 

ground contact is located at the rear of the device, on the truck, and 

visible from the back of the device when out of the circuit breaker 

compartment. (Figure Set 3.3).

Summary of Contents for AM-4.16-GT

Page 1: ...er 2016 Effective September 2017 AM 13 8 GT Ground and Test Device Cable or Hard Bus Type Device Available Cable Type Device Shown AM 4 16 GT Ground and Test Device Hard Bus Type Device GE AM Cable or...

Page 2: ...ffice should be consulted Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eato...

Page 3: ...SHINGS AND DISCONNECTING CONTACT ASSEMBLIES 17 4 3 INTERLOCKS 17 4 4 GROUNDING CONTACTS 17 SECTION 5 INSPECTION INSTALLATION 18 5 1 EXAMINATION FOR DAMAGE 18 5 1 1 NAMEPLATE VERIFICATION 18 5 2 DEVICE...

Page 4: ...HIS DEVICE MUST BE DEVELOPED BY THE USER WARNING SATISFACTORY PERFORMANCE OF THESE GROUND AND TEST DEVICES IS CONTINGENT UPON PROPER APPLICATION CORRECT INSTALLATION AND ADEQUATE MAINTENANCE THIS INST...

Page 5: ...r Hard Bus Application Ground and Test Device Table 2 GE AM 4 16 Ground and Test Device Dimensions Hard Bus Application G T Device Type Existing Circuit Breaker Rated Continuous Current at 60 Hz Amps...

Page 6: ...or Hard Bus Application Ground and Test Device Table 3 GE AM 4 16 Ground and Test Device Dimensions Hard Bus Application G T Device Type Existing Circuit Breaker Rated Continuous Current at 60 Hz Amp...

Page 7: ...and Test Device Table 4 GE AM 13 8 Ground and Test Device Dimensions Cable or Hard Bus Application G T Device Type Existing Circuit Breaker Rated Continuous Current at 60 Hz Amps A B C D E AM 13 8 12...

Page 8: ...enclosure before performing any maintenance Failure to do so could result in electrical shock leading to death severe personnel injury or property damage Do not leave the Ground and Test Device in an...

Page 9: ...s and to the ground connections provided on the G T device Grounding Shorting Bars If applicable AM 4 16 Style 94G2105H29 AM 13 8 Style 94G2100H30 Three grounding shorting bars are furnished only on h...

Page 10: ...8 500 Cable Type Device 1200 2000 810 13 8 500 1200 830 13 8 750T Cable Type Device Single Terminal Set 1200 2000 935 Note N All G T devices listed in this table are hard bus type dual terminal devic...

Page 11: ...est Device Figure 3 3 a Front External View of GE AM 4 16 250 G T Device Hard Bus Type Device 1 8 7 3 4 6 5 9 2 Front External View 1 Primary Disconnects 4 Bushing Knob Holder 7 Grounding Cable 2 Code...

Page 12: ...eaton com GE AM Cable or Hard Bus Application Ground and Test Device Figure 3 3 b Rear External View of GE AM 4 16 250 G T Device Hard Bus Type Device Rear External View 1 Lifting Points 3 Ground Con...

Page 13: ...www eaton com GE AM Cable or Hard Bus Application Ground and Test Device Front External View 1 Primary Disconnects 3 Lock Out 2 Code Plate 4 Kirk Key Interlock Figure 3 3 c Front External View of GE A...

Page 14: ...N September 2017 www eaton com GE AM Cable or Hard Bus Application Ground and Test Device Figure 3 3 d Rear External View of GE AM 13 8 G T Device Hard Bus Type Device Rear External View 1 Lifting Poi...

Page 15: ...e or Hard Bus Application Ground and Test Device Front External View 1 Primary Disconnects 3 Code Plate 5 Grounding Cable 2 Lock Out 4 Kirk Key Interlock 6 Cable Grounding Connection Figure 3 3 e Fron...

Page 16: ...N September 2017 www eaton com GE AM Cable or Hard Bus Application Ground and Test Device Figure 3 3 f Rear External View of GE AM 13 8 G T Device Cable Type Device Rear External View 1 Lifting Points...

Page 17: ...Ground and Test Device consist of six silver plated conductors Solid Stab type primary disconnecting contacts at the ends of the conductors provide means for connecting and disconnecting the G T devi...

Page 18: ...s with silver plated copper conductor knobs Figure 3 3 Primary disconnecting contacts are attached to the knobs these primary disconnects are configured to engage the circuit breaker compartment prima...

Page 19: ...e plate is located on the left hand side of the G T as one faces the device located approximately half way back approximately six inches from the floor Figure 5 4 Interference blocking is provided by...

Page 20: ...bus bar Figure 3 1 e to the internal terminal corresponding to each phase Figure 5 8 Grounding bar can only be installed one way Take care to align the mounting bolts with the integral nut block behi...

Page 21: ...ides of the circuit breaker compartment This is the disconnect position To elevate the G T device position the elevating control selector switch on the elevating motor to RAISE Engage the elevating mo...

Page 22: ...ee cloth If a solvent is required to cut dirt use isopropyl alcohol Hardware Visually inspect all hardware Replace any damaged or missing hardware with parts equivalent to those provided with the Grou...

Page 23: ...epending upon the service severity and continuity requirements Each customer should develop his own level based on operating experience 7 1 1 ORDERING INSTRUCTIONS Always specify the Ground and Test D...