background image

26

Instruction Book    IB019009EN   November 2017   www.eaton.com

AK-2-25, AK-2A-25, & AK-3A-25 LV-VSR

Breaker-To-Motor Starter Conversion

SECONDARY CIRCUIT:

WARNING

BEFORE PERFORMING SECONDARY INSULATION CHECK PLACE A JUMPER 

ON THE CONTACTOR COIL ASSEMBLY POINTS (A) TO (B). FAILURE TO DO 

SO MAY RESULT IN DAMAGE TO THE SOLID STATE RECTIFIER IN THE COIL 

ASSEMBLY.

1.  Ensure that a jumper is placed on contactor coil assembly 

points (A) to (B).
2.  Connect all points of the secondary disconnect pins with a 

shorting wire. 
3.  Connect Current Transformers with a shorting wire and 

connect them to the frame.
4.  Connect the high potential lead of the test machine to the 

secondary block. 
5.  Ground the LV-VSR frame. 
6.  Starting with zero, increase the voltage to 1200 Vac RMS, 60 

Hz. Maintain the voltage for one minute. 
7.  Successful withstand indicates satisfactory insulation 

strength of the secondary control circuit. 
8.  Remove ALL shorting wire on Current Transformers and 

secondary block before placing unit back into service. 
9.  Remove jumper from contactor coil assembly points (A) to 

(B).

WARNING

FAILURE TO REMOVE ALL SHORTING WIRE FROM CURRENT 

TRANSFORMERS AND SECONDARY CONNECTIONS MAY CAUSE INJURIES 

AND EQUIPMENT DAMAGE.

6.7  MECHANISM CHECK

Make a careful visual inspection of the mechanism for any loose 

parts such as bolts, nuts, pins, rings, etc. Check for excessive wear 

or damage to the LV-VSR components. Operate the LV-VSR several 

times electrically to verify operation.

6.8  LUBRICATION

All parts that require lubrication have been lubricated during the 

assembly with molybdenum disulphide grease. Cutler-Hammer 

No. 53701QB. Over a period of time, this lubricant may be pushed 

out of the way or degrade. Proper lubrication at regular intervals is 

essential for maintaining the reliable performance of the mechanism.  

The LV-VSR should be re-lubricated once a year. The locations shown 

in Figure 6-2 should be lubricated with a drop of non-synthetic light 

machine oil.  After lubrication, operate the LV-VSR several times 

manually and electrically.

6.9  PRIMARY CIRCUIT RESISTANCE CHECK

Since the main contacts are inside the vacuum chamber they remain 

clean and require no maintenance at any time. 
The dc resistance of the primary circuit may be calculated by 

measuring the voltage drop across the circuit. To check the primary 

circuit resistance remove the LV-VSR from the switchgear, close the 

LV-VSR and pass at least 10A dc through one of the breaker’s poles. 

Measure the voltage drop across the primary contacts and calculate 

the resistance. Repeat for the remaining two poles.

6.10  MAGNET OPERATING RANGE

If the magnet chatters, look for mechanical interference that 

prevents the magnet itself may be misaligned. The magnet gap can 

be seen from the left and right sides with the help of a flashlight. 

A screwdriver inserted into one of the long slots can be used as 

a lever to put a corrective set into the mounting plate around the 

magnet. It should not be necessary to do this unless the contactor 

has been damaged and it can be seen that the armature does not fit 

against the magnet. A poor magnet to armature fit usually produces 

a high dropout voltage and/or chatter.
Mechanical interference can be produced by various incorrect 

adjustments. Two specific points to check are:
A. Armature travel incorrect, causing the contact springs to be 

compressed into a solid, non-resilient “tube” that stops the 

crossbar rigidly. Refer to Eaton’s Electrical Services and Systems for 

assistance.
B. The auxiliary contact mounting brackets are mis-adjusted, so that 

a contact plunger bottoms solidly before the magnet seals. When 

the contactor is fully sealed closed, there should still be a small 

amount of travel remaining for the plungers. 

L63 Auxiliary Contact Adjustment

The normal .34 inch pretravel gap for the L63 auxiliary contact 

(normally-closed) is important. If the gap is too big, the “hold” 

winding of the operator coil will not be inserted as the contactor 

closes, and the pickup winding will burn out, because the pickup 

winding is only intermittenly rated. If the gap is too small, the 

hold winding will be inserted too soon, reducing the force to 

“hold” before the contactor is closed, and producing an oscillation 

like a doorbell. In a particular contactor, the .34 gap may need 

slight adjustment to avoid these problems. The key is not the 

measurement, but the performance of the magnet.
The auxiliary contacts are not as critical. In the open position, their 

plungers may rest lightly against the operating arm, or may have a 

small clearance.
However, neither of the auxiliary contact polungers should bottom 

solidly in the closed contactor position, as discussed under MAGNET 

OPERATING RANGE. If required, the auxiliaries can be adjusted by 

reseting their mounting brackets in their slotted holes. Adjust the 

L63 by loosening the two slotted hexagonal washer head screws 

that hold the L63 mounting bracket, repositioning and tightening. 

These bracket mounting screws are accessible from the top side of 

the contactor and are recognized by the slotted holes under their 

heads.

Summary of Contents for AK-2-25-LV-VSR-425A

Page 1: ...Instruction Book IB019009EN AK 2A 25 LV VSR 425A Shown November 2017 Supersedes July 2017 Effective AK 2 25 AK 2A 25 AK 3A 25 LV VSR Breaker To Motor Starter Conversion ...

Page 2: ...ns of this equipment do not purport to be covered by these instructions If further information is desired by purchaser regarding his particular installation operation or maintenance of particular equipment contact a local Eaton representative DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information recommendations descriptions and safety notations in this document are based on Eaton s ...

Page 3: ...6 5 3 MANUAL OPERATIONAL CHECK 18 5 4 ELECTRICAL OPERATIONAL CHECKS 18 SECTION 5 A INSTALLATION OF AK 2 25 LV VSR 19 5 A 1 CELL MODIFICATION INSTRUCTIONS 19 5 A 2 COMPARTMENT DOOR MODIFICATIONS 19 5 A 3 INSERTION PROCEDURE 20 5 A 4 REMOVAL PROCEDURE 21 SECTION 5 B INSTALLATION OF AK 2A 25 LV VSR 22 5 B 1 CELL MODIFICATION INSTRUCTIONS 22 5 B 2 INSERTION PROCEDURE 22 5 B 3 REMOVAL PROCEDURE 23 SECT...

Page 4: ...on through the use of micro electronic packaging technology The Overload Relay comes standard with Trip Class 10 15 and 20 trip characteristics and Manual or Manual Automatic Reset The V201 Vacuum Contactor is designed for the control of inductive or non inductive loads at voltages between 200 and 600 ac The fuses have a micro switch mounted to the body of the fuse which provides blown open indica...

Page 5: ...aton com AK 2 25 AK 2A 25 AK 3A 25 LV VSR Breaker To Motor Starter Conversion Table 2 AK 2 25 LV VSR Dimensions Device Type Existing Breaker Rated Continuous Current at 60 Hz Amps A B C D E F G AK 2 25 LV VSR 425A 18 05 3 50 5 00 8 00 20 41 17 10 3 55 ...

Page 6: ...otor Starter Conversion E G F C D A B B Table 3 AK 2A 25 AK 3A 25 LV VSR Dimensions AK 2A 25 LV VSR Shown Device Type Existing Breaker Rated Continuous Current at 60 Hz Amps A B C D E F G AK 2A 25 LV VSR 425A 16 29 3 50 4 50 8 12 20 19 18 00 3 55 AK 3A 25 LV VSR 425A 16 29 3 50 4 50 8 12 20 19 18 00 3 55 ...

Page 7: ...ve the LV VSR from the enclosure before performing any maintenance Failure to do so could result in electrical shock leading to death severe personnel injury or property damage Do not work on a LV VSR with the secondary test coupler engaged Failure to disconnect the test coupler could result in an electrical shock leading to death personnel injury or property damage Do not use a LV VSR as the sole...

Page 8: ...idual pipe rollers Once a LV VSR has been inspected for shipping damage it is best to return it to its original shipping crate until it is ready to be installed in the Metal Enclosed Switchgear When a LV VSR is ready for installation a lifting harness in conjunction with an overhead lift or portable floor lift can be used to move a LV VSR If the LV VSR is to be lifted position the lifting device l...

Page 9: ...Starter Conversion Front External View 1 Overload Relay Access 5 Racking Handle 9 Guide Rail 2 Open Operator 6 Lifting Point 10 Lock Out Tag Out 3 Contactor Status Indicator 7 Secondary Contacts 4 Contactor Operations Counter 8 Handle Pins Figure 3 2 Front External View of AK 2 25 LV VSR 1 8 9 10 6 7 3 2 4 5 ...

Page 10: ...A 25 AK 3A 25 LV VSR Breaker To Motor Starter Conversion Rear External View 1 Secondary Contacts 4 Guide Rail 7 Handle Pins 2 Primary Disconnects 5 Rear Position Stop 3 V201 Vacuum Contactor 6 Lifting Point Figure 3 3 Rear External View of AK 2 25 LV VSR 2 5 4 3 1 1 7 4 6 ...

Page 11: ...Breaker To Motor Starter Conversion Figure 3 4 Front External View of AK 2A 25 LV VSR 1 8 8 5 6 7 3 2 4 Front External View 1 Overload Relay Access 4 Contactor Operations Counter 7 Secondary Block Shim 2 Open Operator 5 Lifting Point 8 Rollers 3 Contactor Status Indicator 6 Secondary Contacts ...

Page 12: ... 25 AK 2A 25 AK 3A 25 LV VSR Breaker To Motor Starter Conversion Figure 3 5 Rear External View of AK 2A 25 LV VSR 2 3 1 1 1 5 6 5 4 Rear External View 1 Secondary Contacts 3 V201 Vacuum Contactor 5 Rollers 2 Primary Disconnects 4 Lifting Point 6 Code Pin 425A Shown ...

Page 13: ...environment immune coil shell which also contains a full wave bridge When ac is connected directly to terminals A and B on the coil shell the magnet excitation is unfiltered dc The magnet will not chatter as ac magnets sometimes do but at less than rated voltage it may hum slightly A normally closed Type L63 auxiliary contact set to open slightly before the armature fully closes is connected to te...

Page 14: ...C VSR SECONDARY CONTACT PIN NUMBER POSITION SWITCH CLOSED IN TEST AND TEST AND CONNECT CONNECT POSITIONS OPEN IN BETWEEN LEGEND FU Ma CS C CS T R S R B A L63 COIL AUX CONT M MR1 C D T MR1 A1 A2 OL PS1 Y AOS S A Y 7 8 T Y Mb T 7 8 Ma a MR1 a MR1 a MR1 a MR1 b MR1 b MR1 b 33 51 61 71 72 62 52 34 24 n o n o n c n c 6 4 4 6 C1 N C 95 96 43 44 13 14 n o n o 5 1 5 1 N C C T TRIP OPEN RELAY Ma CONTACTOR ...

Page 15: ...uses can interrupt faults up to 200 000 Amperes RMS symmetrical current The fuses are Ferraz Shawmut type J AJT600EIB current limiting DO NOT replace the fuses with any other type fuse The fuses have been tested in conjunction with the V201 vacuum contactor Blown Fuse Indication The fuses have a micro switch mounted on the body of the fuse This switch activates when a fuse blows If the LV VSR expe...

Page 16: ... in a 3 phase and single phase form The 3 phase and single phase configured device allows four trip class selections 10 20 30 and 10A Figure 5 6 shows the C440 with four trip class selections 3 Refer to Figure 5 5 or 5 6 C440 relay features include a push pull button for trip and test a push button for reset and the full load current dial Adjacent to the FLA dial the C440 electronic overload relay...

Page 17: ... 0 The C440 FLA setting may also be determined from Table 6 Note N The overload relay allows trip settings that exceed the 425 ampere continuous current rating of the LV VSR Therefore dial settings above 3 5 are not allowed 7 Figures 5 5 and 5 6 are provided for setting assistance For the C440 the overload relay settings are the same regardless of motor service factor Note N The LV VSR is shipped ...

Page 18: ...st be applied remotely or by a control switch located at the switchgear To open the LV VSR either send a remote open signal press the trip plate on the LV VSR or press the test button on the overload relay Perform several close open operations to ensure reliable and constant electrical operation WARNING DO NOT ATTEMPT TO INSTALL OR OPERATE A LV VSR UNTIL A VACUUM INTEGRITY TEST IS PERFORMED Move t...

Page 19: ...A 1 Installing Cell Modification Template Figure 5 A 2 Marking The Cutting Area With Marker Figure 5 A 3 Smoothing The Cut Area With A File 2 Using a felt tip pen mark the right lip of the switchgear using the cutout located in the cell code rejection cutting template Figure 5 A 2 3 Remove the cell code rejection CuttingTemplate from the switchgear 4 Using the appropriate tools cut out the area ma...

Page 20: ...L INJURY OR EQUIPMENT DAMAGE DO NOT ATTEMPT TO INSTALL OR OPERATE A LV VSR UNTIL A VACUUM INTEGRITY TEST IS PERFORMED INSERTION 1 Ensure that the starter is open 2 Place the Starter on the channels of the switchgear enclosure with the guides on the sides of the starter level with the channels Slide the Starter part way into the enclosure The Starter will be obstructed by a position stop at the bot...

Page 21: ...AK 2 25 LV VSR Lock Out Tag Out Figure 5 A 10 AK 2 25 LV VSR in Connect Position 5 A 4 REMOVAL PROCEDURE DANGER LV VSR MUST BE IN THE OPEN POSITION PRIOR TO OPENING CELL DOOR FAILURE TO DO SO MAY CAUSE SEVERE INJURY DEATH OR EQUIPMENT DAMAGE 1 Either remotely or locally open the LV VSR prior to attempting to remove it from the switchgear enclosure 2 Open the cell door 3 Pull the racking handle up ...

Page 22: ...arters the rightmost drill bushing will be used as a guide on 120 amp size starters Figure 5 B 1 AK 2A 25 LV VSR Cell Modification 425A Modification Shown 5 B 2 INSERTION PROCEDURE Note N The secondary blocks are factory equipped with shims on both sides of the LV VSR Figure 3 4 If the secondary blocks are not at the correct distance and cause interference remove the shims by removing the three 25...

Page 23: ... jackscrew handle onto the shaft located on the left side of the enclosure above the position indicator 3 Rotate the jackscrew handle counter clockwise from the Connect position through the Test position and stop when the position indicator reads DISC and the crank can no longer turn 4 Remove handle and open enclosure door 5 Pull the Starter out to its limits by rotating the two rack lock links an...

Page 24: ...UARD AGAINST ELECTRICAL SHOCK 6 3 2 CONTACT WEAR ALLOWANCE Contact material vaporizes from the contact faces during every interruption and condenses inside the bottle This is normal and is provided for by over travel or wear allowance When the contactor is fully closed there is a gap between the pivot plate and the bottle nuts As the contacts wear this gap decreases When any gap goes below 0 020 i...

Page 25: ...If there is a breakdown the contactor should be replaced before placing the LV VSR in service 7 After the high potential is removed discharge any electrical charge that may be retained particularly from the center shield of vacuum interrupters To avoid any ambiguity in the ac high potential test due to leakage or displacement capacitive current the test unit should have sufficient volt ampere capa...

Page 26: ...breaker s poles Measure the voltage drop across the primary contacts and calculate the resistance Repeat for the remaining two poles 6 10 MAGNET OPERATING RANGE If the magnet chatters look for mechanical interference that prevents the magnet itself may be misaligned The magnet gap can be seen from the left and right sides with the help of a flashlight A screwdriver inserted into one of the long sl...

Page 27: ... overcurrent or short circuit Unit experienced an overcurrent and that exceeded OL Relay set point Control Circuit Fuses blown Control Power Secondary Diconnects Handle VSR will not operate if racking handle is not in the full down position Undesirably Closes Control Circuit Close Circuit CS C Shorted Fails To Trip Control Circuit Fuses blown Control Power Secondary Disconnects T Relay Undesirably...

Page 28: ...he service severity and continuity requirements Each customer should develop his own level based on operating experience 7 1 1 ORDERING INSTRUCTIONS 1 Always specify the LV VSR rating information and general order number from the nameplate 2 Describe the item give the style number and specify the quantity required 3 Specify the voltage for electrical components 4 Specify the method of shipping des...

Page 29: ...29 Instruction Book IB019009EN November 2017 www eaton com AK 2 25 AK 2A 25 AK 3A 25 LV VSR Breaker To Motor Starter Conversion ...

Page 30: ...levard Cleveland OH 44122 United States Eaton com 2017 Eaton All Rights Reserved Printed in USA Publication No IB019009EN November 2017 Eaton is a registered trademark All trademarks are property of their respective owners ...

Reviews: