background image

3

Instruction Leaflet 

IL15465

Effective May 2011

A200 Size 3 or 4, 3  Pole Motor Controller

EATON CORPORATION

 www.eaton.com

Heaters should be selected on the basis of the actual full load 

current and service factor as shown on the motor nameplate or 

in the manufacturer’s published literature. When the service factor 

of the motor is 1.15 to 1.25, select heaters from the heater 

application table. If the service factor of the motor is 1.0, or there 

is no service factor shown, or a maximum of 115% protection is 

desired, select one size smaller heater than indicated. When motor 

and overload relay are in different ambients and when using non-

compensated overload relays, select heaters from the table using 

adjusted motor currents as follows: decrease rated motor current 

1 % for each °C motor ambient exceeds controller ambient. 

Increase rated motor current 1% for each °C controller ambient 

exceeds motor ambient.

COIL

The A200 motor controller is available with a single or dual 

voltage coil. When equipped with a single voltage coil, the 

contactor is wired as shown in Figure 6. A connection diagram 

for a dual voltage coil is shown in Figure 4. When supplied with 

a dual voltage coil, the motor controller is normally wired for the 

high voltage connection. The wiring may be changed to the low 

voltage connection by removing and reconnecting the jumpers as 

illustrated below.

Reviews: