 setUPS 

 
Firmware upgrade procedure 

 

 

Eaton®setUPS_9PX_1-1_1to3k_firmware_upgrade_rev_02

 

Page 5/13

 

Click on “

Install

” 

  

 

And on “

Finish

” 

 

 

 

And the Eaton

®

 setUPS starts. 

 

 If Eaton

®

 setUPS is already installed, from 

All Programs

 menu, open setUPS  

                        

 

 

At the startup, the software searches for the connected UPS 

                  

 

 

Summary of Contents for 9PX 1:1

Page 1: ...Eaton setUPS Firmware upgrade procedure Eaton setUPS_9PX_1 1_1to3k_firmware_upgrade_rev_02 Page 1 13 UPS model 9PX 1 1 1 to 3kVA Date 02 09 2016 ...

Page 2: ... Contents 1 Download the software setUPS and the firmware if receiving this document by email 2 UPS connection 3 Launch setUPS 4 Go to Bypass 5 setUPS firmware menu 6 Firmware selection 7 Confirmation 8 Upgrade process 9 Upload success 10 Return to normal state 11 Go back to Normal 12 Trouble shooting ...

Page 3: ... firmware Go to the Power Quality Website http powerquality eaton com EMEA Support Software Drivers default asp Select your product 9PX 1 3kVA and select your solution type Firmware Configuration Click on Download 9PX UPS 1 3kVA Firmware Updates configuration And click on the required link Firmware file setUPS software Upgrade instructions ...

Page 4: ...ct a communication cable to the UPS unit on USB or RS232 DB9 port on the back of the UPS Then connect the cable to your computer 3 Launch setUPS For a first time Eaton setUPS installation double click on the exe file and valid the User Account Control message by Yes The installer opens click on Next Read and click on Accept ...

Page 5: ...n setUPS_9PX_1 1_1to3k_firmware_upgrade_rev_02 Page 5 13 Click on Install And on Finish And the Eaton setUPS starts If Eaton setUPS is already installed from All Programs menu open setUPS At the startup the software searches for the connected UPS ...

Page 6: ...02 Page 6 13 and as soon as communication is established the product is identified 4 Go to Bypass On the UPS go to the menu CONTROL and select Go to bypass The Bypass indicator orange illuminates and a click noise comes from the UPS relay WARNING loads are powered but not protected anymore ...

Page 7: ...on setUPS_9PX_1 1_1to3k_firmware_upgrade_rev_02 Page 7 13 If there is a Maintenance Bypass HotSwap MBP connected to the UPS switch to Bypass position 5 setUPS firmware menu On the left menu select Firmware section the available firmware appears ...

Page 8: ...re_upgrade_rev_02 Page 8 13 If the firmware list is empty copy paste the downloaded firmware in the target folder My Documents Eaton setUPS firmware click on the button 6 Firmware selection Click on the latest firmware file to select it and then on the Upload firmware button ...

Page 9: ... output is OFF but load still powered during the upgrade select Yes to continue 8 Upgrade process The UPS emits a beep and transfers into Boot loader mode The firmware will then be erased and then rewritten into the UPS During the flash process the status led AC line Battery Bypass Fault on the UPS cycle a progress bar is displayed on LCD and a beep is emitted every 10s ...

Page 10: ...3k_firmware_upgrade_rev_02 Page 10 13 And on setUPS window the firmware upgrade steps appear 9 Upload success When the firmware flash process is done the UPS emits a long beep The setUPS issues a pop up to let know the firmware flash has been successful click on OK ...

Page 11: ...firmware_upgrade_rev_02 Page 11 13 10 Return to normal state The setUPS reverts back to the UPS information section The firmware version should now reflect the latest version 11 Go back to Normal If there is a hotSwap MBP go back to UPS ON position only green LED is ON ...

Page 12: ...pgrade_rev_02 Page 12 13 In order to protect the loads on the UPS go back to the menu CONTROL and select Go to normal After confirmation the AC line indicator green illuminates Once the UPS is online the loads are protected Press ESC button twice to come back to the main screen ...

Page 13: ...the firmware It is not possible to transfer the UPS in Bypass mode it displays Canceled instead of Done UPS is in Frequency converter mode it is necessary to disable this mode Menu Settings In Out settings Output frequency UPS must be OFF to modify this setting The firmware upgrade is stopped during the process restart the firmware upgrade process and the upload starts again The upgrade through US...