Table 4. Configuration Settings (continued)
Default Setting
Available Settings
Description
Output frequency
[50Hz] [60Hz] [Auto sensing]
NOTE
Numerical settings configured in Standby mode take effect
immediately. Auto sensing and settings configured outside of
Standby mode take effect after the next power off and restart.
Selecting auto sensing disables the battery start feature until the
first successful startup on utility power.
For 9910-E35 and 9910-E36 models, the default auto sensing runs
once to set the output frequency and then uses the detected
setting for all subsequent startups.
For 9910-E66 and 9910-E67 models, the default auto sensing runs at
each startup to set the output frequency.
Auto sensing
NOTE
When configured
for auto sensing, the
UPS uses the optimal
detected setting for
frequency.
Overload alarm level
[10%] [20%] [30%]...[100%]
If 100%, the UPS issues an Output Overload alarm at load >100%.
NOTE
Configure the Output Overload Level 1 to alert you before
the UPS reaches its rated capacity limits.
100%
Automatic start delay
[Off] [0s] [1s] [2s]...[32767s]
See “Configuring Load Segments” on page 31.
0s for Load Segment 1
1s for Load Segment 2
Automatic on battery
shutdown
[Off] [0s] [1s] [2s]...[32767s]
See “Configuring Load Segments” on page 31.
Off
Site wiring fault alarm
[Enabled] [Disabled]
Disabled
Bypass voltage low
limit
[-6%] [-7%]...[-20%] of nominal
The Bypass operation is disabled if the measured bypass voltage
level is below the nominal output voltage (-15%).
NOTE
The Qualify Bypass setting might overrule the Bypass
Voltage Low Limit setting.
-15% of nominal
Bypass voltage high
limit
[+6%] [+7%]...[+20%] of nominal
The Bypass operation is disabled if the measured bypass voltage
level is above the nominal output voltage (+10%).
NOTE
The Qualify Bypass setting might overrule the Bypass
Voltage High Limit setting.
+10% of nominal
Summary of Contents for 9910
Page 1: ...Powerware Series Eaton 9910 UPS and EBM User s Guide ...
Page 2: ......
Page 3: ...Powerware Series Eaton 9910 UPS and EBM User s Guide ...
Page 26: ...INSTALLATION Eaton 9910 UPS and EBM User s Guide S P 164000005 Rev 2 18 ...
Page 44: ...OPERATION Eaton 9910 UPS and EBM User s Guide S P 164000005 Rev 2 36 ...
Page 60: ...UPS MAINTENANCE Eaton 9910 UPS and EBM User s Guide S P 164000005 Rev 2 52 ...
Page 75: ......
Page 76: ... P 1640000052 P 164000005 2 ...