Eaton 93PR 60-1200 kW UPS
Installation and Operation Manual
39
Copyright © 2021 Eaton Corporation plc. All rights reserved.
Table 3-7: Rated and Maximum Currents for Rated Power and Voltage (unit:A)
UPM QTY
Input Current
Output current
Battery
(Rated)
Battery
(Max)
380
400
415
380
400
415
4*60kW
380
361
348
365
346
334
521
625
4*62.5kW
396
376
362
380
361
348
543
651
5*60kW
475
451
435
456
433
417
651
781
6*60kW
570
541
522
547
520
501
781
938
7*60kW
665
631
609
638
606
584
911
1094
8*60kW
760
722
696
729
693
668
1042
1250
8*62.5kW
791
752
725
760
722
696
1085
1302
9*60kW
855
812
783
820
779
751
1172
1406
10*60kW
950
905
870
915
870
835
1302
1563
11*60kW
1045
992
956
1003
953
918
1432
1719
12*60kW
1140
1083
1043
1094
1039
1002
1563
1875
13*60kW
1235
1173
1130
1185
1126
1085
1693
2031
14*60kW
1329
1263
1217
1276
1212
1169
1823
2188
15*60kW
1424
1353
1304
1367
1299
1252
1953
2344
16*60kW
1519
1443
1391
1459
1386
1336
2083
2500
17*60kW
1614
1534
1478
1550
1472
1419
2214
2656
18*60kW
1709
1624
1565
1641
1559
1503
2344
2813
19*60kW
1804
1714
1652
1732
1645
1586
2474
2969
20*60kW
1899
1804
1739
1823
1732
1669
2604
3125
NOTE
Bypass fuse type should be greater than 10 times rated I
2
t 20ms.