Eaton 93PR 60-1200 kW UPS
Installation and Operation Manual
37
Copyright © 2021 Eaton Corporation plc. All rights reserved.
The selection of wire diameter needs to take into account the future power upgrade of UPS.
Table 3-5: Maximum Recommended Multi-core Cable Sizes (unit:mm
2
)
UPM QTY
Rectifier
input
UPS
output
Bypass
input
N*
Battery*
PE*
4*60kW
2*150
2*150
2*150
3*150
4*150
6*150
4*62.5kW
2*150
2*150
2*150
3*150
4*150
6*150
5*60kW
2*150
2*150
2*150
3*150
4*150
6*150
6*60kW
2*150
2*150
2*150
3*150
4*150
6*150
7*60kW
3*150
3*150
3*150
5*150
5*150
8*150
8*60kW
3*150
3*150
3*150
5*150
5*150
8*150
8*62.5kW
3*150
3*150
3*150
5*150
5*150
8*150
9*60kW
3*240
3*240
3*240
5*240
4*240
6*240
10*60kW
3*240
3*240
3*240
5*240
4*240
6*240
11*60kW
4*240
4*240
4*240
6*240
6*240
8*240
12*60kW
4*240
4*240
4*240
6*240
6*240
8*240
13*60kW
5*240
5*240
5*240
8*240
8*240
8*240
14*60kW
5*240
5*240
5*240
8*240
8*240
10*240
15*60kW
5*240
5*240
5*240
8*240
8*240
10*240
16*60kW
5*240
5*240
5*240
8*240
8*240
10*240
17*60kW
6*240
6*240
6*240
9*240
8*240
10*300
18*60kW
6*300
6*300
6*300
9*300
8*300
10*300
19*60kW
6*300
6*300
6*300
9*300
8*300
10*300
20*60kW
6*300
6*300
6*300
9*300
8*300
10*300
*:The UPS busbars wiring needs to be evenly divided (see
to
for the location of the busbars).
Summary of Contents for 93PR Series
Page 1: ...60 1200 kW Installation and Operation Manual Eaton 93PR UPS ...
Page 2: ......
Page 142: ......
Page 143: ...614 40061 01 ...