25-75 kW
User's and Installation Guide
83
8.5 UPS Environmental Specifications
Table 8-5: UPS environmental specifications
Acoustic Noise at 1 m
< 65 dBA in double conversion
< 55 dBA in ESS
Ambient UPS Storage Temperature Range
From -25 °C to +55 °C in the protective package*
Ambient Service Temperature Range, (UPS)
From +5 °C to +40 °C*,
No output power derating required.
Relative Humidity Range
5 to 95 %, no condensation allowed
Maximum Service Altitude
5 to 95 %, no condensation allowed
Maximum 2000 m (6600 ft) with 1 % derating per
each additional 100 m.
*Maximum recommended operating and storage temperature with VRLA batteries is +25 °C.