Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03
1
C
Chhaapptteerr 11 IInnttrroodduuccttiioonn
The Eaton
®
93PM-L 60 kW, Four-Wire uninterruptible power supply (UPS) is a true online, continuous-duty,
transformerless, double-conversion, solid-state, three-phase system, providing conditioned and uninterruptible
AC power to protect the customer's load from power failures.
The Eaton 93PM-L UPS online power protection system is used to prevent loss of valuable electronic
information, minimize equipment downtime, and minimize the adverse effect on production equipment due to
unexpected power problems.
The Eaton 93PM-L UPS continually monitors incoming electrical power and removes the surges, spikes, sags,
and other irregularities that are inherent in commercial utility power. Working with a building's electrical
system, the UPS system supplies clean, consistent power that sensitive electronic equipment requires for
reliable operation. During brownouts, blackouts, and other power interruptions, batteries provide emergency
power to safeguard operation.
The Eaton 93PM-L UPS is available with up to three Uninterruptible Power Modules (UPMs) integrated in one
cabinet. Each UPM is rated for a maximum of 20 kW. The system maximum rating is 60 kW. To deliver greater
reliability, a UPS with two or more UPMs can provide N+1 redundancy up to a maximum of 40 kW. Should one
UPM become unavailable or require servicing, the remaining UPMs supply the load instead of transferring to
bypass.
The UPS is housed in a single free-standing cabinet, with safety shields behind the door for hazardous voltage
protection. Power wiring is installed through the bottom of the cabinet with an optional sidecar available for top
entry wiring.
shows the Eaton 93PM-L UPS,
shows the Eaton 93PM-L UPS with a left or right-
mounted Top Entry Wiring Sidecar, and
shows the Eaton 93PM-L UPS with a left or right-mounted
Bypass Sidecar (SIAC-B).
NOTE
Startup and operational checks must be performed by an authorized Eaton Customer
Service Engineer, or the warranty terms specified on the product's resources page
become void. See
for details. This service is offered as part of the
sales contract for the UPS. Contact an Eaton service representative in advance (a
minimum two-week notice is required) to reserve a preferred startup date.
11..11
U
UP
PS
S S
Sttaannddaarrdd FFeeaattuurreess
The UPS has many standard features that provide cost-effective and consistently reliable power protection. The
descriptions in this section provide a brief overview of the UPS standard features.
11..11..11
IInnssttaallllaattiioonn FFeeaattuurreess
•
Line-up-and-match or standalone configurations
•
Power wiring can be routed through the bottom of the cabinet in standalone configurations or alternately
through the top when configured with an optional accessory sidecar
•
Battery wiring can be run internally through the left or right sides of the UPS cabinet in line-up-and-match
configurations
•
Easily accessible mechanical terminals located at the bottom front of the cabinet reduce installation time
•
Control wiring can be routed through the top or bottom of the UPS cabinet, or through the left or right
sides of the UPS cabinet in line-up-and-match configurations
•
Built-in casters for easy cabinet placement
•
Cabinet bolt holes are provided for permanently mounting the UPS using optional front and back or left and
right side floor mounting bracket kits
Summary of Contents for 93PM-L Series
Page 4: ......
Page 164: ...P 16400071103 P 164000711 03...