Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03
133
CAUTION
Do not attempt to restart the system after the REPO until the cause of the shutdown has been identified and
cleared.
2.
To deactivate the REPO switch in preparation for restarting the UPS, insert the supplied key and rotate
clockwise until the red pushbutton releases (see
). To remove the key, rotate the key back to the
vertical position.
3.
Restart the UPS by following the procedure in paragraph
Starting the UPS in Double Conversion Mode
or
Starting the UPS in Bypass Mode
.
WARNING
Power is present inside the UPS cabinet until the upstream input feeder circuit breakers and battery breakers
are opened. Wait at least 5 minutes before accessing internal components.
Figure 77. REPO Operation
Activated
(Pushbutton locked into place.)
Deactivated
(Unlock pushbutton to release.)
66..44
M
Muullttiippllee EExxtteerrnnaall P
Paarraalllleell S
Syysstteem
m O
Oppeerraattiioonn
NOTE 1
If an Integrated Battery Cabinet (IBC) is installed, refer to its installation and operation
manual, listed in
Chapter 1
Introduction, For More Information
section, for IBC
battery breaker location.
NOTE 2
If a Sidecar Integrated Accessory Cabinet (SIAC) or an Integrated Accessory Cabinet
(IAC) is installed, refer to its installation and operation manual, listed in
Chapter 1
Introduction, For More Information
section, for operating instructions.
NOTE 3
This unit is a four-wire device. The loss of a single input phase will be considered a
complete loss of input power and discharge the battery to provide power to the load.
66..44..11
S
Sttaarrttiinngg tthhee P
Paarraalllleell S
Syysstteem
m iinn D
Doouubbllee C
Coonnvveerrssiioonn M
Mooddee
To start the UPS system:
1.
Close all Module Output Breakers (MOBs).
2.
Close the UPS input feeder circuit breaker.
Summary of Contents for 93PM-L 60-1