UPS Installation Plan and Unpacking
surfaces only.
• The UPS operating temperature at ambient 0-40°C.
• The battery operating temperature at ambient 20-25°C.
• Relative humidity at 95%, non-condensing
• The system must be installed in a temperature and humidity controlled indoor area free
of conductive contaminants.
• The system If the UPS is to operate at altitude higher than 1000m (3300ft),
contact an Eaton service representative for further important information on
operating on higher altitude.
Failure to follow guidelines may void your warranty.
The UPS equipment operating environment must meet the weight requirements shown in Table 3-1 and the
size requirements shown in Figure 3-1 through Figure 3-5. Dimensions are in millimetres (inches).
Table 3-1. UPS Cabinet Weights
Model
Weight ( kg)
Net Weight
Gross Weight
Descriptions
93E XL-10I-9Ah-MBS
770
859
93E XL-15I-9Ah-MBS
770
859
93E XL-20I-9Ah-MBS
770
859
93E XL-30I-9Ah-MBS
780
869
93E XL-40I-9Ah-MBS
790
879
I- Internal battery
MBS-with internal
MBS
The UPS cabinet uses forced air cooling to regulate internal component temperature. Air inlets are in the front of the
cabinet and outlets are in the back of the cabinet. Allow clearance in front of and in back of the cabinet for proper air
circulation. The clearances required around the UPS cabinet are shown in Table 3-2 and Table 3-3
Table 3-2. UPS Cabinet Clearances
From Top of Cabinet
At least 300 mm (12") working space
From Front of Cabinet
At least 900 mm (36") working space
From Back of Cabinet
At least 600 mm (36") working space
From Right Side of Cabinet
See Table No: 3-3
From Left Side of Cabinet
See Table No: 3-3
8
Eaton 93E XL UPS (10-40kVA, 380/400/415V) Installation and Operation