Table 4-5. N o r m a l l y - C l o s e d REPO Wire Terminations
From REPO Station(s)
Switch Contact Block
(Either Block)
To REPO Terminal Block
on Back of UPS Cabinet
Wire Size
Tightening Torque
1,2 NC
See Figure 4-15 for wiring
Twisted Wires (2)
14-22AWG
3,4 NC
(0.5
-2.0mm
2
)
7 lb in
(0.8 Nm)
REPRO
1
Switch
(NC)
2
Figure 4-15. Normally-Closed REPO Switch Wiring
Twisted
Wires
1
2
REPO
TB
3
4
36
Eaton 93E XL UPS (10-40kVA, 380/400/415V) Installation and Operation